The BE1-32R Directional Overpower Relay and the BE1-32O/U Directional
Over/Underpower Relay are solid-state devices which provide versatility
and control in protecting machines against reverse power flow,
underpower and overpower conditions.

ADVANTAGES
Measures Real Power - El cos Θ.
Wide variety of input configurations are available including single-phase
and three phase, 3 and 4 wire systems.
Sensing ranges available from 0.5 to 6000 watts secondary.
Instantaneous, definite and inverse timing characteristics available.
Low input sensing and supply burdens.
Qualified to the requirements of
IEEE C37.90.1-1989 and IEC 255 for fast transient and surge
withstand capability;
IEC 255-5 for impulse.
UL recognized under Standard 508. UL File #E97033.
Five year warranty.
The BE1-32R Directional Overpower Relay and the BE1
32 O/U, Directional Over/Underpower Relays sense real
power flow (El cos Θ). These relays are solid-state
devices designed for use in single-phase or three-phase
systems to provide equipment protection for overpower
and/or underpower or to be used for supervisory control
of circuits. Both relay configurations may be used to
monitor either forward or reverse power. In the following
application examples, single-phase connections are
shown for simplicity.
APPLICATION EXAMPLES
The BE1-32 relays (R and O/U) are typically used in
applications where excessive power flow in the tripping
direction is indicative of undesirable situations. Typical
examples are discussed below. Notice: This product is
not recommended for power factors below 0.10. Contact
Basler Electric for recommended products.
EXAMPLE 1 - ANTI MOTORING
In this example, the power relay is used to protect the
prime mover rather than the generator. When an ac
generator, operating in parallel with a power system,
loses prime mover torque, it remains in synchronism
with the system and continues to run as a synchronous
motor drawing sufficient power from the system to drive
the prime mover. Sustained motoring can cause severe
damage to the prime mover. The Directional Power
Relay, with its wide sensitivity range, can detect levels of
reverse real power flow as low as 0.5 Watts secondary
and provide an alarm or trip the unit off line (See Figure
1). In this example, single phase sensing is usually
considered sufficient, since motoring is a balanced
condition.
EXAMPLE 2 - COGENERATOR CONTROL
Given that a co-generation system has automatic
engine controls, auto synchronizer, and automatic kW
and kVar controls, the system will virtually operate by
itself. The only functions not readily apparent are the
start/stop signals to the generators. Two system con
figurations using a Power Relay may be utilized to
generate contact closures for start and/or stop signals.
The first configuration (Figure 2) shows a power relay
connected to the utility to sense kW. The pickup point of
the relay is set at the maximum desired utility power
level. If the power relay contact closes, the generator
will be started and automatically paralleled with the
utility system. A time delay of 15 seconds or more is
generally included in the start circuit to ignore
transient overload conditions.