Glossary of terms and transition types
Available
A source is defined as available when it is within its undervoltage/
overvoltage/underfrequency/overfrequency/unbalance(if applicable)
setpoint ranges for the nominal voltage and frequency setting.
Unavailable
A source is defined as failed when it is outside of its undervoltage/
overvoltage/underfrequency/overfrequency/unbalance (if applicable)
setpoint ranges for the nominal voltage and frequency setting.
Normal source
The normal source is defined as the source that is preferred. The
preferred source setting allows the operator to select source 1.
source 2 or NONE as the preferred source. If NONE is chosen, the
preferred source or the normal source will be the source that is
presently attached to the load. The default is set as being source 1
as the preferred and normal source.
In-phase operation
The in-phase operation of an automatic transfer switch is an open
transition transfer. It will allow a transfer between two available
sources if the phase angle has a difference of five degrees or less.
See section 1.5.4 for more details.
As shown in the feature list of Appendix A, there are three scenarios
for in-phase:
32C= In-phase default to load voltage decay
32D= In-phase default to time delay neutral
32F= In-phase
The user setpoints for in-phase transition are as follows:
• Disabled (in-phase not used)
• Alarm on synchronization fail (will not switch and will show an alarm)
• Fallback to open on synchronization fail (To TDN or LVD)
For example, with the setpoint at fallback, using a two position
contactor, the switch will transfer to the other source if no synchroni
zation occurs, whereas a three position contactor will allow the use
of TDN or load voltage decay.
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved