Functions/features/options
The primary function of the ATC-900 is to accurately monitor power
sources and provide the necessary intelligence to operate a transfer
switch in an appropriate and timely manner. In addition, the ATC-900
provides useful real-time and historical data, reliable two-way
communications, and programming through the device’s faceplate
or Modbus RTU. The ATC-900 features digital signal processor (DSP)
technology to provide and maintain superior precision and versatility
during both programming and data access.

Operational simplicity
From installation, to programming, to usage, the ATC-900 was
designed with operational simplicity in mind. Only two styles need
to be considered, regardless of input/output requirements or system
voltages and frequencies. The ATC-900 provides the functionality of
numerous other devices combined in one package that mounts in
less than 7 by 11 inches of panel space.
The user-friendly front panel interface simplifies routine operation,
setpoint programming, and data presentation. A large color display
provides flexibility and ease of use. Front panel membrane pushbut
tons are used to navigate the intuitive menus and screens. A single
unit status LED at the top of the faceplate provides an immediate
indication as to the device’s operational mode. Pressing the Help
button provides immediate user assistance messages on the front
panel display.
The ATC-900 is communications ready, including Modbus RTU,
Ethernet (via external communication module), and USB for thumb
drives (memory sticks).
Standard and optional features
A variety of programmable features are available to meet a wide
array of application requirements. Individual features or feature
combinations provide the information required to tailor switches to
individual needs.
Unlike earlier controllers, the ATC-900 comes with standard features
that are ready to use, with the exception of closed transition, current
metering, and Ethernet. Another advancement is that there are four
(4) standard inputs and four (4) standard outputs that the operator
can easily program by choosing from a wide array of predefined
functions. Additional inputs and outputs can be added in groups of
four (4) up to sixteen (16) for a maximum of twenty (20) in total.
Consult section 4.2.1 for I/O specifications.