AN-X2 Modes of Operation
There are two AN-X2 modes of operation:
• Maintenance mode. The AN-X2 runs the maintenance firmware at startup. It
performs diagnostics (memory tests, etc), copies any changes from the microSD card.
If there are no errors, it starts the AN-X2 in production mode.
• Production mode. This is the normal runtime mode of operation.
Prevent Electrostatic Discharge
The module is sensitive to electrostatic discharge.
WARNING!
Electrostatic discharge can damage integrated circuits or
semiconductors. Follow these guidelines when you handle the module:
• Touch a grounded object to discharge static potential
• Do not touch the connector pins
Power
AN-X requires a DC power input of anywhere from 12 to 24 VDC.
Left to right the pins on the power connector are chassis ground, negative voltage and
positive voltage.
The chassis ground should be connected.
Power consumption is 200 mA @ 12VDC or 100mA @ 24VDC.
The part number for the power connector is Phoenix MSTB 2.5/3-ST-5.08
Contact us if you need a suitable wall adapter.
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com