A-B 1407-CGCM Combined generator control module

From:A-B | author:Mr.Chen | Time :2024-07-22 | 1169 view: | 🔊 Click to read aloud ❚❚ | Share:

Installation requirements

This device is intended for overvoltage applications of category II in industrial environments of pollution class 2 (as defined in IEC publication 60664-1).

The device must be mounted vertically as it contains a heat sink. Any other mounting angle will reduce the heat dissipation capability of the device and may result in premature failure of critical components.

The device can be mounted anywhere as long as the ambient temperature does not exceed the rated ambient conditions or clearance requirements.

Clearance requirements for CGCM equipment are

- 63.5 mm (2.5 inches) of clearance is required on both sides of the unit when mounted.

- 101.6 mm (4 in.) clearance is required above and below the unit when mounted.

Electrical Connections

The connection of the CGCM device depends on the application and the excitation programme. It is not possible to use all inputs or outputs in a given installation. Incorrect wiring may result in damage to the equipment.

Connect the terminals of the CGCM unit with copper wire rated at no less than 600V. General purpose wire rated for a minimum temperature of 105 °C (221 °F) may be used.

All wire must be copper. Select circuit wires according to good design practice.

The wire gauge ranges listed in the terminal block label instruction table indicate the physical capabilities of the connector.

Terminals for CGCM devices are located on the front, bottom, and right side panels of the device.

The nine-pin connector on the bottom of the unit is used for communication between CGCM devices in a redundant system. The recommended torque for the terminal screws is 1 N-m (9 lb-in).

Terminals that are used as shield wire landings are found on multiple terminal strips. Shielded terminals with the same name are connected together internally, but are not connected to a protective ground or any internal device circuit.

Excitation power supply

The excitation power supply is connected to the PMG terminals whether it is connected to the generator output (parallel excitation) or to the PMG.

The shunt excitation input is connected to the voltage transformer (VT).

The PMG inputs are located on TB1 and are labelled PMG A, PMG B and PMG C, indicating the respective phase relationship.

The single-phase excitation power supply must be connected to terminals PMG A and PMG C. The PMG inputs require twisted pair connections.

A twisted pair shielded cable is required for the PMG input.

See wiring diagram below.

Chassis Ground

The terminal marked CH GND on TB4 is the chassis ground terminal. There is also a grounding screw on the underside of the mounting flange that connects internally to the CH GND terminal.

Connect the chassis ground to the lower stud on either side of the unit with a minimum 2.6 mm2 (10 AWG) copper wire.

Connect the chassis ground to the lower stud on either side of the unit with a minimum 2.6 mm2 (10 AWG) copper wire and to the CH GND terminal with a 1.6 mm2 (14 AWG) copper wire.

When installed in a system with other CGCM devices, use a separate wire from each device to connect to the ground bus.

Analogue Inputs

The CGCM unit provides a number of analogue inputs for regulating and controlling independent or parallel generator systems. Each input is summarised below.

Generator Voltage Sense Input

The CGCM unit senses generator voltage through a voltage transformer (VT) mounted on the generator output leads.

The CGCM unit uses the voltage measured through the generator voltage sensing input for the generator voltage,

VAR and/or power factor regulation, kW and kVAR load sharing, synchronisation, metering and protection.

The input accepts signals with up to 40% total harmonic distortion (THD) and can be connected for single-phase and three-phase applications.

The generator voltage input is internally scaled by the CGCM unit according to its transformer configuration settings.

The generator voltage sense inputs are labelled V Gen A, V Gen B, V Gen C and V Gen N.

Bus Voltage Detect Inputs

The voltage measured via the bus voltage detection input is used to synchronise the generator with the bus.The CGCM device detects the bus voltage via VT.

  • CTI 2556 16-Channel Isolated Thermocouple Input Module
  • CTI 2557-A 16-Channel RTD Input Module
  • CTI 2500S-27-1750 Slice I/O, Ethernet, RS232/485, 900MHz, 2DIO / 4UAI / 2AI (MATURE)
  • CTI 2500S-26-1750 Slice I/O, Ethernet, RS232/485, 900MHz, 8DIO / 2UAI (MATURE)
  • CTI 2500S-23-1750 Slice I/O, Ethernet, RS232/485, 900MHz, 4DI / 4DO / 2UAI / 2AO (MATURE)
  • Beckhoff ELM3504-0030 | EtherCAT Terminal, 4-channel analog input, measuring bridge
  • Beckhoff ELM3504-0000 | EtherCAT Terminal, 4-channel analog input, measuring bridge
  • Beckhoff ELM3502-0030 | EtherCAT Terminal, 2-channel analog input, measuring bridge
  • Beckhoff ELM3502-0000 | EtherCAT Terminal, 2-channel analog input, measuring bridge
  • Beckhoff ELM3348-0033 | EtherCAT Terminal, 8-channel analog input, temperature
  • Beckhoff ELM3348-0030 | EtherCAT Terminal, 8-channel analog input, temperature
  • Beckhoff ELM3348-0003 | EtherCAT Terminal, 8-channel analog input, temperature, thermocouple
  • LENZE Cabinet PC series Industrial PCs
  • LENZE Embedded Line series Industrial PCs
  • LENZE Command Station series Industrial PCs
  • LENZE 3200 C Controller
  • HIMA H6200A DIN rail Safety Analog Isolation Module Transmitter Circuit
  • Eaton CORPORATION IQMESIIN1 METER
  • Eaton DT223UGK Heavy duty double-throw non-fused safety switch
  • Eaton 5884-1400 6-Digit Dual Preset Control W/ Batch Control
  • Eaton 1023843 Power Circuit Board 94V
  • EATON ES4P-221-DRXD1 24VDC NSMP
  • Eaton DH222NWK heavy duty fusible safety switch
  • Eaton Touch Panel 10.1 inch XV-303-10-C00-A00-1C
  • Eaton RDF200J-3 Bussmann series RDF fused rotary disconnect switch
  • EATON CORPORATION A200M2CACD A200 NEMA Motor Control
  • Eaton SPD160208Y3J Surge Protection Device
  • EATON CORPORATION SPD160208Y3K SURGE SUPPRESSOR
  • EATON DILM400/22 (RA250) 200KW Coil Voltage/Coil 110-250V 40-60Hz/DC
  • Eaton XV-430-10TVB-1-10 139902 Touch Panel
  • EATON CORPORATION D820MPM HMI
  • EATON PXG900 Power Xpert Insight Gateway 900
  • Eaton Durant 5882-7 Digital Counter loc2D3
  • EATON AXCELIS 1220-0012-0002 DISK VACUUM DI CONTROLLER
  • Eaton 1383B-6501 80 Series Photoelectric Sensor Head
  • Eaton FDC2100L Series C molded case switch
  • Eaton XV-430-10TVB-1-10 139902 Touch Panel
  • Eaton FD3200L circuit breaker
  • Eaton Touch Screen Control Panel X-152-D6-10TVRC-10
  • EATON VICKERS EEA-PAM-523-A-32 02-326001 POWER AMPLIFIER
  • Saacke Seavis HMI 03 EATON XV-102-B6-35TQR-1AL-PLC HMI Touch Panel
  • EATON MTL E05016 DIGITAL INPUT EUROCARD E05516-2134
  • Eaton HFD3150 3P 150A 600VAC Circuit Breaker
  • Eaton HMIVU06CUNB1 HMi Operator Interface, RS-232, 5.6"
  • Cutler-Hammer/ Eaton Panelmate PowerPro 5785 with cables LCD monitor
  • Eaton D100CA40 40 I/O Micro PLC 115VAC Input Triac Output
  • EATON CUTLER HAMMER 66D2032GX1 MP-3000 PROTECTION RELAY
  • EATON R9L3200FJ Rotary Disconnect Switch
  • EATON CORPORATION E51CLT16PCU Switch
  • Aerotech Modular System Control Console
  • Aerotech TV Series Transformers
  • Aerotech TM5 Transformer Module (500 watts)
  • Aerotech TM3 Transformer Module
  • Aerotech UFM Noise Filter Module
  • Aerotech MFM10-2 Motor filter module
  • Aerotech MFM10-1 Motor filter module
  • Aerotech MPG Handwheel Pendant
  • Beckhoff ELM3348-0000 | EtherCAT Terminal, 8-channel analog input, temperature
  • Beckhoff ELM3344-0033 | EtherCAT Terminal, 4-channel analog input, temperature
  • Beckhoff ELM3344-0030 | EtherCAT Terminal, 4-channel analog input, temperature
  • Beckhoff ELM3344-0003 | EtherCAT Terminal, 4-channel analog input, temperature
  • Beckhoff ELM3344-0000 | EtherCAT Terminal, 4-channel analog input, temperature
  • Beckhoff ELM3246-0000 | EtherCAT Terminal, 6-channel analog input, temperature
  • Beckhoff ELM3244-0000 | EtherCAT Terminal, 4-channel analog input, temperature
  • Beckhoff ELM3148-0000 | EtherCAT Terminal, 8-channel analog input, multi-function
  • Beckhoff ELM3146-0000 | EtherCAT Terminal, 6-channel analog input, multi-function
  • Beckhoff ELM3144-0000 | EtherCAT Terminal, 4-channel analog input, multi-function
  • Beckwith Electric M-5072 Retrofit Kit For M-4272 Digital Motor Bus Transfer System
  • Beckwith Electric M-3919A Graphic Display Unit/ Human Machine Interface
  • Beckwith Electric M-4172 Digital Motor Bus Transfer System
  • Beckwith Electric M-3904B Remote Monitoring Module
  • Beckwith Electric M-3410A Intertie/Generator Protection Relay
  • Beckwith Electric B-1612 Adapter
  • Beckwith Electric B-1652 Adapter
  • Beckwith Electric B-1685 Adapter
  • Beckwith Electric M-2035 Analog to Digital Interface Module
  • Beckwith Electric B-2291 Digital Input Guard
  • Beckwith Electric M-2406 Recloser Control Adapter Chassis
  • Beckwith Electric M-3908 Universal Contact Input Adapter
  • Beckwith Electric M-3801D IPS Plot Software
  • Beckwith Electric M-7651A D-PAC
  • Beckwith Electric M-2979 Recloser Control Cabinet
  • Beckwith Electric M-0359 SYNCROCLOSER MOD512
  • Beckwith Electric M-2001C-6ELFA Tap Changer Controller Voltage Regulator Control
  • Beckwith Electric M-0124 TERMINAL BOARD ADAPTER PLATE 13 POS
  • Beckwith Pride M-0296C 3ph Programmable Relay
  • Beckwith Electric M-0388 Syncrocloser Check Relay
  • M-0170A AC Current Relay Beckwith Electric
  • Beckwith Electric Intertie Protection M-3520 Instruction Manual
  • M-3311 M-3311 7113 BECKWITH ELECTRIC TRANSFORMER PROTECTION RELAY
  • Pride M-0296b 3 phase Programmable Relay Beckwith Electric Co
  • Beckwith Electric M3310 Integrated Transformer Protection Panel
  • Beckwith M-0145 First Customer Protector
  • Beckwith Electric M-0296C 3 phase Programmabel Relay
  • Beckwith Electric M-0389 VOLTAGE VERIFIER
  • M-3425 M-3425-A1DE BECKWITH ELECTRIC GENERATOR PROTECTION RELAY SL
  • Beckwith Electric M-0420 Multifunction Relay Protection Module 48VDC
  • M-3430 M-3430M0D515 BECKWITH ELECTRIC GENERATOR PROTECTION RELAY
  • Beckwith Electric Tapchanger Control M-0067E
  • Beckwith M-2001D-6L4S20C0S0X Tap Changer Control Surplus
  • BECKWITH ELECTRIC M3425A-STD1 Generator Protection 85-280VDC
  • Beckwith Electric High Speed Sync-Check Relay #M-0245C Mod #22 (NIB)
  • Beckwith Electric M-7679 R-PAC
  • Beckwith Electric TAPCHANGER CONTROL M-2001C-6SL
  • Beckwith P-2216 Generator Protection Power Main Board 450-00258 B-1038
  • Beckwith Electric P-2216 Generator Protection Power Main Board 450-00258 B-1038
  • Beckwith Electric M-2293 Tap Changer Control
  • Beckwith Electric M-4272-6AB1EH0 Integrated Synchronizing System Motor Bus Transfer
  • Beckwith Electric TapChanger Control M-2001B Series M-2001B-C2 Surplus
  • Beckwith Electric P-1939 Generator Protection Relay Annunciator Panel B-0898 Rev A-2
  • Beckwith Electric M-3311A 8 Output D-0179 60-140 VAC Transformer Protection
  • Beckwith Electric B-2355 Adapter Kit
  • Beckwith Electric B-2203 Adapter Kit
  • Beckwith Electric B-2271 Adapter Kit
  • Beckwith Electric B-2293 Adapter Kit
  • Beckwith Electric B-6200A-U1 Hinge Kit
  • Beckwith Electric M-2032B Battery Charger/Power Supply
  • Beckwith Electric M-2900A Tapchanger Control Cabinet
  • Beckwith Electric M-6200A Digital Voltage Regulator Control
  • Beckwith Electric M-0124 Surface Mounting Adapter
  • Beckwith Electric B-2048 Resistor Assembly
  • Beckwith Electric M0169A Auxiliary Current Transformer Units
  • Beckwith Electric M-0121 and M0169A Auxiliary Current Transformer Units
  • Beckwith Electric M-0404 Voltage Isolation Transformer
  • Beckwith Electric M-0329B LTC Backup Control
  • Beckwith Electric M-0001 Battery Transient Suppressor
  • Beckwith Electric Module d’Équilibrage en Parallèle M-0115A
  • Beckwith Electric M-0115A Parallel Balancing Module