Features
Remote LCD annunciator for use with Simplex® model:
4100ES and 4100U fire alarm control panels
Legacy products 4100. 4120. and 4020 fire alarm control
panels, and 4100/4120 Universal Transponders
Information display features:
Maintained display of first alarm is available with
4100ES and with 4100U at software revision 11.11 or higher
Wide viewing angle, super-twist LCD technology with
green LED backlighting
Two lines of 40 characters each
LED status indicators
During battery backup, backlighting is disabled until
there is switch activity

Controls include:
Switches for system acknowledge, alarm silence, and
system reset
Four programmable control switches
Lamp/LCD test
Wiring information:
RUI (Remote Unit Interface) communications require a
single twisted wire pair (see p. 3 for more information)
Separate wiring is required for 24 VDC control panel power
Flush mount on standard electrical boxes Options:
2975-9206. Surface mount box
4603-9111. Brushed stainless steel trim
UL Listed to Standard 864
Description
Remote Control and Annunciation is provided using
an 80 character, back-lit, alphanumeric display.
Information is presented in clear, descriptive English
language and includes: Point Status (alarm, trouble, etc.);
Alarm Type (smoke detector, manual station, etc.);
Number of System Alarms, Supervisory Conditions,
and Trouble Conditions; and a Custom Location Label.
Wiring. A single twisted wire pair provides serial RUI
communications that also supports other Simplex serial
annunciators on the same wire pair.
Multiple Indications. Alarm, Supervisory, and Trouble
conditions are also indicated by dedicated LEDs and a
tone-alert audible sounder. Each condition has a dedicated
acknowledge push-button switch that silences the
tone-alert but leaves the LED on until all conditions in
that category are restored to normal. Switch operation is
either globally or individually acknowledgeable,
determined by the control panel operation.
Repeated operation of the appropriate acknowledge
switch will scroll the LCD display showing activity in the
sequence of occurrence. The tone-alert also pulses to
indicate the operation of any of the push-button switches.
Consult local code requirements for guidance in
determining applications and location of the 4603-9101
LCD annunciator.