Features
Compatible with Simplex ES Net and 4120 fire alarm networks
Satisfies a variety of new and retrofit applications
4.3 in. (109 mm) diagonal color touchscreen display:
• Provides detailed system status and point information.
• Supports dual language selection, including unicode character
languages.
• A custom background display appears when operation is normal.
Eight point zone/relay module:
• For each point, you can select as an IDC input or Relay output.
Class A IDCs require two points, one out and one return. One
module is standard and you can field install up to three additional
modules for a total of four 8 point zone/relay modules for each
system.
• You can configure each point on the IDC/Relay module as a
control relay rated 2 A at 30 VDC resistive as either normally open
or normally closed.
• Power comes directly from the power supply or through the
optional 25 VDC Regulator Module
• You can select the IDC end-of-line (EOL) resistor value from a wide
range of resistance values for retrofit convenience

Electrically isolated IDNet 2 addressable initiating device SLC:
• Provides built-in short circuit isolation for monitoring and
control of TrueAlarm analog sensors and IDNet communications
monitoring and control devices. For use with either shielded or
unshielded, twisted or untwisted single pair wiring. Outputs are
Class A or Class B.
• Standard panel signaling line circuit (SLC) provides up to 100
addressable points. Optional additional loop expansion modules
provide an additional isolated loop with short circuit isolation for
the IDNet 2 channel. Each loop expansion module also provides
an additional 75 addressable points.
Power supply:
• Four notification appliance circuits (NACs), you can select as Class
A or Class B with 6 A total available current
• You can select the NAC EOL resistor value from a wide range of
resistance values for retrofit convenience
• For additional notification power capacity, use a 4009 IDNet NAC
Extender.
• Battery backup charging of up to 33 Ah. Up to 18 Ah for cabinet
mounted batteries and up to 33 Ah for batteries mounted close
nippled, in a remote battery cabinet.
General mechanical:
• Red or platinum cabinet. Rated NEMA 1 and IP30.
4007ES Listings reference:
• UL 864 - Control Units, System (UOJZ). Control Unit Accessories,
System, Fire Alarm (UOXX). Control Units, Releasing Device Service
(SYZV)
• UL 2017 - Emergency Alarm System Control Units (CO detection),
(FSZI)
• ULC-S559 - Central Station Fire Alarm System Units (DAYRC)
• ULC-S527 - Control Units, System, Fire Alarm (UOJZC). Control Unit
Accessories, System, Fire Alarm (UOXXC). Control Units, Releasing
Device Service (SYZVC)
Software feature summary:
• Current and previous panel configuration is maintained in on
board memory
• An internal Ethernet service port is available for service computer
connections to perform configuration updates, downloads and
uploads, report downloads, and update system software
• You can use the internal USB interface with a memory stick to
store job revisions, update revised jobs and panel software, and
save detailed system reports from the panel.
Optional modules and connections include:
• Fire alarm network interface card (NIC) for ES Net or 4120 network
• Peer-to-peer network communications, supports either Class B or
Class X operation
• Point or Event DACT assembly for Connected Services Gateway
• Up to two additional IDNet 2 addressable device output loop
connections with short circuit fault protection and with 75
additional point capacity each.
• Front mounted 32 LED and 32 LED/switch annunciator with
custom label inserts. LEDs are programmable for up to 32
IDC zones of alarm and trouble annunciation or other custom
annunciation requirements.
• Remote LED annunciator support through remote user interface
(RUI) communications port for use with UTP wiring.
• Dual RS-232 ports for printer, PC annunciator, or third party interface.
• Alarm relays and auxiliary relays.
• City connections, with or without a disconnect switch.
• 4009 IDNet NAC Extenders to extend NAC capability for power and
distance
• Battery brackets for seismic area protection.