If open circuit detection is enabled, the module tests for an open-circuit
condition. If it detects an open-circuit, over-range, or under-range
condition, the module sets a unique bit in the channel status word
and causes the channel status LED to flash.
The SLC processor reads the converted thermocouple or millivolt data
from the module at the end of the program scan, or when
commanded by the ladder program. After the processor and module
determine that the data transfer was made without error, the data can
be used in your ladder program.
Module Operation
The module’s input circuitry consists of eight differential analog
inputs, multiplexed into an A/D convertor. The A/D convertor reads
the analog input signals and converts them to a digital value. The
input circuitry also continuously samples the CJC sensors and
compensates for temperature changes at the cold junction (terminal block).
IMPORTANT When using multiple thermocouples, the potential
between any two channels cannot exceed the
channel-to-channel differential voltage (12.5 volts).
For more information, see Appendix B.