Changing main contacts, arc chutes and coils
When changing the AF coil with its PCB (printed circuit board) care must be
taken to avoid ESD damage.
Before any dismantling of the contactor:Make dead by, turning off the contactor.
Opening the main circuit by turning off the main switch, if any, or by removing the
main fuses in all three phases. To protect against making attempt, open also the con
trol circuit.
Trouble shooting
examples of common reasons for contactors not working properly
Voltage drop during start up of the motor Voltage drop to less than 85 % of nominal
voltage for 5 to 10 ms can be enough for the contactor to start opening.
Also,other disturbances in the control voltage such as poor relay contacts or too small
control transformer/power supply could be responsible for this problem.
The result of these voltage problems can be increased
contact wear and also lead to welding of main contacts.
With the AF technology these problems are avoided.
Poor voltage to coil
Control voltage less than 85% during pick up may not be enough to safely close the
contactor and can cause the coil to meltdue to over heating. This because the coil
is designed to withstand the inrush current for a limited time only. One common
reason is when the coil supply is taken from the main supply were high current
is causing the voltage to drop. Too high continuous control voltage could also
cause the coil to melt. See picture below for typical failure.
Direct on line (across-the-line) motor starting.
Current peaks used by heavy duty starting- If the application requires a high level
of torque during start-up, for example a big fan or a pump, it is important that the
contactor’s making capacity and short time withstand current are capable of handling
the starting current and current peak.