Product Description
The WIOC is a native DeltaV I/O node that supports up to 100
wireless devices. The cards install on a 2-wide carrier, with each
card having its own Smart Wireless Field link. The WIOC can be
commissioned in a simplex mode if no redundancy is needed.
The WIOC allows redundancy to be completed later, when
needed – online and bumpless.
The WIOC carrier has two Ethernet IO Ports that connect to the
DeltaV Area Control Network and are available with copper or
fiberoptic media. The Smart Wireless Field links are connected
to the I/O card using a 4-conductor cable. The cable has a pair of
wires for power and a pair for the communication to the
field link.
The WIOC uses the Smart Wireless technology supported by
WirelessHART devices and a Self-Organizing Network.
No wireless expertise is required; devices automatically find
the best communication paths with Adaptive Mesh Routing.
Network continuously monitors paths for
degradation and repairs itself.
Adaptive behavior provides reliable, hands-off
operation and simplifies network deployments,
expansion, and reconfiguration.
If an obstruction is introduced into the mesh network, devices
will find the best alternate communication path. This alternate
path is automatically created by the network management
software and the device information will continue to flow.
WirelessHART Integration with the DeltaV
System and AMS Device Manager
Native integration with the DeltaV system enables you to
autosense the WIOC and easily commission it for seamless
integration with all DeltaV applications: Explorer, Diagnostics,
and Control Studio. The WIOC is commissioned into the DeltaV
I/O network and counts as one of the 300 I/O nodes.
WirelessHART devices can be easily added to a mesh network
using AMS Device Manager to assign the Network ID and
Join Key. Once configured, simply install the device in the
field and it is automatically detected and reconciled through
DeltaV Explorer. The device can be assigned to any one of
four controllers. Each device is also automatically defined
with PlantWeb alerts that proactively report device health to
maintenance personnel, with zero configuration.
This provides added flexibility and accommodates late
changes where control modules may be reassigned to a
different controller.
The Ethernet I/O Ports of the WIOC are the same as DeltaV
CHARM I/O Cards (CIOC) and can be connected with CIOCs
in the DeltaV network topology. The I/O Port for copper
10/100BASE-TX media support a second “cascade” port that
allows a series of WIOCs to be daisy-chained together to
simplify the network design and reduce cost.