Device parameters
General remarks
Microprocessor-based position control in the positioner
optimizes control. The positioner features high-precision
control functions and high operational reliability. Due to their
elaborate structure and easy accessibility, the device
parameters can be quickly adapted to the respective
application.
The total range of parameters includes:
— Operating parameters
— Adjustment parameters
— Monitoring parameters
— Diagnostics parameters
— Maintenance parameters
Operating parameters
The following operating parameters can be set manually if required:
Setpoint signal
0 ... 100 % freely selectable for split-range operation
For 4 ... 20 mA and HART version:
— Signal min. 4 mA, max. signal 20 mA (0 ... 100%)
— Min. range 20 % (3.2 mA)
— Recommended range > 50 % (8.0 mA)
Action (setpoint signal)
Increasing:
Position value 0 ... 100 % = direction 0 ... 100 %
Decreasing:
Setpoint signal 100 ... 0% = direction 0 ... 100%
Characteristic curve (travel = f {setpoint signal})
Linear, equal percentage 1:25 or 1:50 or 25:1 or 50:1 or freely
configurable with 20 reference points.
Travel limit
The positioning travel, i.e. the stroke or angle of rotation, can
be reduced as required within the full range of 0 ... 100 %,
provided that a minimum value of 20% is observed.
Shut-off function
This parameter can be set separately for each end position.
When the respective configured limit value is exceeded, the
shut-off function causes immediate travel of the actuator until
reaching the set end position.
If the value "0" is entered for the corresponding parameter, the
position is further controlled, even in the respective end
position.
Travel time prolongation
This function can be used to increase the max. travel time for
full travel. This time parameter can be set separately for each
direction.
This function can only be used with the pneumatics with the
safety function "fail-safe".
Switching points for the position
You can use these parameters to define two position limits for
signaling (see option "Module for digital position feedback").
Digital output
The alarms generated in the positioner can be polled via the
digital output as a collective alarm.
The desired information can be selected via the operator panel
or remotely via the configuration program.
The output can be set to "active high" or "active low", as
required.
Digital input
For the digital input, one of the following safety options can be
selected. You may use the operator’s panel or configuration
program to select an option.
— No function (default)
— Move to 0 % position
— Move to 100 % position
— Hold previous position
— Disable local configuration
— Disable local configuration and operation
— Disable any access (no local or remote access via a PC)
The selected function is activated when the 24 V signal is no
longer connected to the digital input (< 11 V DC).