The TU842 MTU can have up to 16 I/O channels and 2+2 process
voltage connections. Each channel has two I/O connections and one
ZP connection. The maximum rated voltage is 50 V and maximum
rated current is 3 A per channel.
The MTU distributes the two ModuleBuses to each I/O module and to
the next MTU. It also generates the correct address to the I/O
modules by shifting the outgoing position signals to the next MTU.
The MTU can be mounted on a standard DIN rail. It has a mechanical
latch that locks the MTU to the DIN rail.
Four mechanical keys, two for each I/O module, are used to configure
the MTU for different types of I/O modules. This is only a mechanical
configuration and it does not affect the functionality of the MTU or
the I/O module. Each key has six positions, which gives a total
number of 36 different configurations.
Features and benefits
• Complete instalation of I/O modules using 3-wire connections and field power distribution.
• Up to 16 channels of field signals and process power connections.
• Connections to two ModuleBuses and I/O modules.
• Mechanical keying prevents insertion of the wrong I/O module.
• Latching device to DIN rail for grounding.
• DIN rail mounting