Real-time bi-directional server-client communication Symphony® Plus Gateway Software
(SGS) is a configurable component of Symphony® Plus that provides real-time bi-directional
communication between ModbusTCP devices and Symphony® Plus Controllers.
The Symphony® Plus Gateway Software (SGS) con
sists of two main components: Engineering Utilities
and Runtime software. The Engineering Utilities of
SGS provide a full function menu driven interface
that simplifies configuration for startup engineer
ing, commissioning and ongoing maintenance of the
ModbusTCP interface. With first time configura
tions, as only minimum parameters are required, en
gineering hours can be reduced by using the Quick
Config feature to generate the Mapping and Client
Definition tables. Individual interface points can
then be configured using the SGS menus.
The Runtime portion of SGS performs ModbusTCP
communications to other ABB equipment (e.g.
AC500. AC 800M) or 3rd party PLC’s over a 100Mbps
Ethernet network and remote wireless gateways.
The Symphony Plus Gateway Software is licensed
based on the number of function block outputs and
inputs the interface exchanges. SGS uses a mapping
database to define which Modbus data points are to
be exchanged between the Modbus Transfer Tables
and the Harmony function block in the controller’s
configuration. Harmony function blocks typically
contain more information than an equivalent Mod
bus point can support, making it necessary to map
more than one Modbus point to a single Harmony
function block. SGS employs the use of multi-map
ping to allow quality, alarms and values to be fully
defined within the ModbusTCP configuration.
On the ModbusTCP network, connections between
client and server devices are made through TCP
sockets. Depending on the module being used, SGS
can be configured to a maximum of 8 server connec
tions to foreign Modbus clients and 128 client con
nections to foreign Modbus servers.
Features and benefits
• Bi-directional communication in real-time with
Modbus devices
• Support for standard Modbus function codes and
exception codes
• Exception and cyclic data writes
• Fully tunable communication rates
• Diagnostics enable isolation and troubleshooting
of one connection
• Support of online configuration (change in function
blocks of the SGS points) with redundant controllers