Application
The over and undervoltage relay REU 523 is a secondary relay which is connected to the
voltage transformers of the object to be protected. The over and the undervoltage unit
continuously measure the fundamental wave of the phase-to-phase voltages of the object.
On detection of a fault, the relay will start, trip the circuit breaker, provide alarms, record
fault data, etc., in accordance with the application and the configured relay functions.
The overvoltage unit includes low-set stage U> and high-set stage U>> and the undervolt
age unit low-set stage U< and high-set stage U<<. The high-set undervoltage stage can
alternatively be set to evaluate the positive phase-sequence voltage. In addition, the high
set undervoltage stage can be configured to evaluate only one instead of three phase-to
phase voltages.

The protection functions are independent of each other and have their own setting groups
and data recordings. The over and undervoltage functions use conventional voltage trans
former measurement.
An output contact matrix allows start or trip signals from the protection stages to be
routed to the desired output contact.
Design
The relay includes a high-set and low-set overvoltage unit, a high-set and low-set und
ervoltage unit and a circuit-breaker failure protection unit. Further, the relay includes an
HMI module, a self-supervision system and a disturbance recorder.
Overvoltage unit
When the voltage values exceed the set start value of low-set stage U>, the overvoltage
unit will start to deliver a start signal after a ~60 ms’ start time. When the set operate time
at definite-time characteristic or the calculated operate time at inverse definite mini
mum time (IDMT) characteristic elapses, the overvoltage unit will deliver a trip signal.
When the voltage values exceed the set start value of high-set stage U>>, the overvoltage
unit will start to deliver a start signal after a ~50 ms’ start time. When the set operate time
at definite-time characteristic or the calculated operate time at IDMT characteristic
elapses, the overvoltage unit will deliver a trip signal.
The low-set and the high-set stage of the overvoltage unit can be given either a defi
nite-time or an IDMT characteristic. At IDMT characteristic, two time/voltage curve
groups, A and B, are available.
It is possible to block the tripping of an over voltage stage by applying an external binary
input signal to the relay.
The high-set stage can be set out of operation. This state will be indicated by dashes on the
LCD and by “999” when the set start value is read via serial communication.
wechat/whatsapp:
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved