Feeder protection and control REF630
REF630 has been designed to protect overhead line and cable feeders in utility
and industrial power distribution systems, including radial, looped and meshed
distribution networks, with or without distributed power generation.
Application
REF630 has been designed to be the main
protection for overhead lines and cable feeders,
in either isolated neutral, resistance-earthed,
compensated or effectively earthed distribution
networks. The comprehensive feeder
management relay offers four predefined
configurations, intended for open/closed ring
feeder applications, radial overhead/mixed line
feeder applications, ring/meshed feeder
applications and bus sectionalizers.
The earth-fault protection has been significantly
extended, now including not only directional
and non-directional, transient/intermittent,
wattmetric and admittance-based, but also both
harmonics and multifrequency admittance-based
earth-fault protection. The new additions take
the earth-fault protection to new heights,
creating an extensive earth-fault protection
portfolio. In addition, the sensitivity of the
intermittent earth-fault protection has been
significantly improved and reactive power
undervoltage protection added.
REF630 also includes a fault locator that locates
short circuits in radial distribution networks and
earth faults in effectively and low-resistance
earthed ones. If the fault current is as high as or
higher than the load current, earth faults in
isolated neutral distribution networks will also
be located.
Product highlights
• Extensive earth-fault protection portfolio with
unique multifrequency admittance-based
protection for higher sensitivity and selectivity
• Advanced and fast fault location of short
circuits and earth faults