Station communication
The 611 series protection relays support the IEC 61850 and
Modbus® communication protocols. Operational information
and controls are available through these protocols. However,
some communication functionality, for example, horizontal
communication between the protection relays, is enabled only
by the IEC 61850 communication protocol.
The IEC 61850 protocol is a core part of the relay as the
protection and control application is fully based on standard
modelling. The relay supports Edition 1 and Edition 2 versions
of the standard. With Edition 2 support, the relay has the latest
functionality modelling for substation applications and the best
interoperability for modern substations. It incorporates also full
support for standard device mode functionality supporting
different test applications. Control applications can utilize the
new safe and advanced station control authority feature.
The IEC 61850 communication implementation supports
monitoring and control functions. Additionally, parameter
settings, disturbance recordings and fault records can be
accessed using the IEC 61850 protocol. Disturbance
recordings are available to any Ethernet-based application in
the standard COMTRADE file format. The relay supports
simultaneous event reporting to five different clients on the
station bus. The relay can exchange data with other devices
using the IEC 61850 protocol.