Introduction
The RDP-110C Remote Display Panel provides remote annunciation of engine
/generator status. When used with Basler Digital Genset Controllers DGC-2020.
DGC-2020ES, DGC-2020HD, DGC-500. or DGC-1000. the RDP 110C provides
compliance with NFPA 110 Level 1 and Level 2 requirements.
The RDP-110C is suitable for use with isolated generators or paralleled generating
systems.
The RDP-110C serves as the successor to the RDP-110. The RDP-110C features
identical functionality in a more compact size, enabling its use in a broader range
of applications. An optional adaptor plate enables convenient replacement of an
RDP-110 with an RDP-110C.

Comprehensive Annunciation Capabilities
The RDP-110C is equipped with the following LED indicators:
• RDP-110C control power applied
• Genset supplying load
• DGC not operating in Auto mode
• Six fixed-function alarms
• Two programmable alarms
• Five fixed-function pre-alarms
• Two programmable pre-alarms
An audible alarm indicates the presence of alarms, pre-alarms, and when the DGC
is taken out of Auto mode. An Alarm Silence pushbutton resets the audible alarm.
Operation of the audible alarm and all visual indicators can be verified with the Lamp
Test pushbutton.
Rugged and Flexible Construction
A rugged, compact metal case provides improved electromagnetic compatibility and
make the RDP-110C resistant to moisture, salt fog, dust, dirt, and chemical
contaminants. Two available mounting configurations provide the option of semi-flush
mounting or surface (projection) mounting. Conduit knockouts on the case enable
the RDP-110C to be used as a “pass-through” or junction box for other site wiring.
Simple Connections
RDP-110C connections consist of control power wiring and wiring for communication
between the DGC and RDP 110C. Two-wire, RS-485 communication between the
RDP-110C and DGC simplifies wiring and ensures electrical noise immunity over long
distances.
Overview
The RDP-110C allows DGC (Digital Genset Controller) users to easily meet
the annunciation requirements of NFPA-110 applications. Simple integration
to the genset control system provides alarm and pre-alarm indication and
annunciation of system status.
Features
• Four programmable LEDs via BESTlogic™Plus
• Annunciation of 17 alarms and pre-alarms as detected by the DGC
• Audible alarm horn
• Lamp Test and Alarm Silence switches
• Power supply inputs for 12 Vdc and 24 Vdc
(local to the RDP-110C)
• RS-485 communications reduces the number of interconnection wires
to four
• Two mounting configurations
• Conduit box included
• Designed for use in harsh environments
Benefits
• Easy customization of alarm and pre-alarm LEDs (two each),
allowing adaptation to various applications while maintaining
NFPA-110 requirements.
• Selection of 12 Vdc and 24 Vdc power supply inputs are standard,
enhancing compatibility with virtually any system while reducing
inventory.
• Two mounting configurations, surface and semi-flush, are available
for easy adaptation to installation requirements.
• Rugged construction makes the RDP-110C the optimal choice for
harsh environments.