Wiring Strain Relief
Tie down points and ratcheting tie wraps are provided to secure the wiring to the PCB mounting plate.
This helps prevent wire strain from being transmitted to the connection at the terminal block and to keep
the wiring from chafing on the cover when tightening and under vibration. Failure to secure the wiring
could result in intermittent connections resulting in intermittent operation or shutdown conditions. Allow for
additional wire service length between the tie down points and the connectors to reduce strain on the wire
at the connector interface and to allow the black pluggable connector to be removed.
Shield Installation Notes
• Wires exposed beyond the shield should be as short as possible, not exceeding 50 mm (2 inches).
• The shield termination wire (or drain wire) should be kept as short as possible, not exceeding 50 mm
(2 inches), and the diameter should be maximized where possible.
• Installations with severe electromagnetic interference (EMI) may require additional shielding
precautions. Contact Woodward for more information.
• Do not ground shield on both ends, except where permitted by the control wiring diagram.
Failure to provide shielding can produce future conditions that are difficult to diagnose. Proper shielding at
the time of installation is required to ensure satisfactory operation of the product.
Control Input
The QuickTrip valves are controlled with the independent trip relay outputs from a trip system logic solver
such as the Woodward ProTechTPS.
Note: When used with the ProTechTPS, external power is not necessary for these inputs. All voltage
and isolation is provided within the ProTechTPS (24 VDC, 0.5 A).
Trip Points:
• If the input voltage drops below14 VDC, then the input will detect a Trip state.
• If the input voltage rises above 15 VDC, then the input will detect a Run state.
Control Input Isolation: 500 VAC from input to chassis.
Wiring Requirements
• Keep this and all other low level signal cables separated from input power cables to avoid
unnecessary coupling (noise) between them.
• Wire Gauge Range: 0.8 to 1.3 mm² / 16 to 28 AWG stranded wire.
• Shielding: The control inputs are unshielded; however, the wires should be kept in a twisted
configuration for noise immunity.
Position Feedback
There are two outputs for valve position feedback on each of the QuickTrip’s three valve modules (12
outputs total). Each of the two outputs features redundant connections. Both TRIP outputs and both RUN
outputs operate as normally open. The outputs can be wired to either switch load from positive supply or
switch load to ground. The user must supply the external 24 V supply for the output to function properly. If
using the Woodward ProTech TPS logic solver, the voltage may be supplied using the on-board discrete
power terminals (24 VDC, 0.050 A).
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved