The range also supports power supply configurations of the AC 800M and S800 I/O based IEC 61508-
SIL2 and SIL3 rated solutions. A Mains Breaker Kit for
DIN Rail is also available for our power supplies and voters.
For updated information regarding this hardware
please visit our Hardware Selector. In the selector
you can compare different communication modules,
AC 800M controllers, S800 IO modules, Select I/O
modules, module termination units, 800xA networks
equipment, power supplies and voters, Panel 800 and
also print your own PDF files.
Power Supplies
The SD83x and SD85x Power Supply Units are designed to meet all the applicable electrical safety
data stated by the EN 50178 harmonized European
Standard Publication and the additional safety and
function data required by EN 61131-2 and UL 508.
The secondary output circuitry is accepted for SELV
or PELV applications.
They are switch-mode Power Supply Units which
convert the mains voltage to 24 volts d.c. These
power supplies can be utilized for non-redundant
and redundant applications. Redundant applications
require diode voting units SS823 or SS832.
With the type SD83x series Power Supply Units,
there is no requirement for the installation of a
mains filter. They provide a soft start feature; power-on of an SD83x will not trip fuses or earth-fault
circuit breakers. The SD822Z is also G3 compliant.
Key Features
• Simple DIN-rail mounting
• Class I Equipment, (when connected to Protective Earth, (PE))
• Over-voltage Category III for connection to primary main TN network
• Protective separation of secondary circuit from primary circuit
• Accepted for SELV and PELV applications
• The output of the units is protected against over
current (current limit) and over voltage (OVP)
• SD834 can be connected in parallel to increase output power
• Both a.c. and d.c. input at SD831 and SD834
• Floating DC-OK relay contact at SD834
Voting Units
The Voting Units SS822Z, SS823 and SS833 have been
specifically designed to be employed as a control
unit within a redundant power supply configuration. The output connections from two Power Supply
Units are connected to the Voting Unit. The Voting
Unit separates the redundant Power Supply Units, supervises the voltage supplied, and generates supervision signals to be connected to the power consumer.
Green LED’s, mounted on the front panel of the voting unit, provide a visual indication that the correct
output voltage is being delivered. Simultaneously
with the green LED illuminating, a voltage free contact closes the path to the corresponding “OK connector”. Voting Unit trip levels, are factory preset.
High Integrity
The AC 800M High Integrity and the connected S880
High Integrity I/O system (including field power)
shall be supplied from a SELV or PELV power supply
(e.g. SD83x) connected through the power voter
SS823. The SS823 Voting Unit has double overvoltage protection circuit, limiting the output voltage to
max 30 VDC. It is also able to detect both short and
open circuit in the voting element.
The SS822Z and SS823 units is also G3 compliant.