Power quality
In the EN standards, power quality is defined through the
characteristics of the supply voltage. Transients, short-duration
and long-duration voltage variations and unbalance and
waveform distortions are the key characteristics describing
power quality. The distortion monitoring functions are used for
monitoring the current total demand distortion and the voltage
total harmonic distortion.
Power quality monitoring is an essential service that utilities can
provide for their industrial and key customers. A monitoring
system can provide information about system disturbances and
their possible causes. It can also detect problem conditions
throughout the system before they cause customer complaints,
equipment malfunctions and even equipment damage or
failure. Power quality problems are not limited to the utility side
of the system. In fact, the majority of power quality problems
are localized within customer facilities. Thus, power quality
monitoring is not only an effective customer service strategy but
also a way to protect a utility's reputation for quality power and
service.
The protection relay has the following power quality monitoring
functions.
• Voltage variation
• Voltage unbalance
• Current harmonics
• Voltage harmonics
The voltage unbalance and voltage variation functions are used
for measuring short-duration voltage variations and monitoring
voltage unbalance conditions in power transmission and
distribution networks.
The voltage and current harmonics functions provide a method
for monitoring the power quality by means of the current
waveform distortion and voltage waveform distortion. The
functions provide selectable short-term 3- or 60- or 300
second sliding average and a long-term demand for total
demand distortion (TDD) and total harmonic distortion (THD).
The phase-specific harmonic content is measured for voltages
and currents, as well as DC component and fundamental
content. The dedicated harmonics measurement page in the
LHMI presents the measurements in a user-friendly manner.
Fault locator
The relay features an optional impedance-measuring fault
location function suitable for locating short circuits in radial
distribution systems. Earth faults can be located in effectively
and low-resistance earthed networks, as well as in
compensated networks. When the fault current magnitude is at
least of the same order of magnitude or higher than the load
current, earth faults can also be located in isolated neutral
distribution networks. The fault location function identifies the
type of the fault and then calculates the distance to the fault
point. The calculations provide information on the fault
resistance value and accuracy of the estimated distance to the
fault point.
Disturbance recorder
The relay is provided with a disturbance recorder featuring up to
24 analog and 64 binary signal channels. The analog channels
can be set to record either the waveform or the trend of the
currents and voltages measured.
The analog channels can be set to trigger the recording function
when the measured value falls below or exceeds the set values.
The binary signal channels can be set to start a recording either
on the rising or the falling edge of the binary signal or on both.
The binary channels can be set to record external or internal
relay signals, for example, the start or trip signals of the relay
stages, or external blocking or control signals. The recorded
information is stored in a nonvolatile memory in COMTRADE
format and can be uploaded for subsequent fault analysis.
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved