Sample conditioning system
The integral stream selector for the NGC8206 allows sampling
up to four (4) different natural gas streams. Up to two of these
sample streams can be designated as the “calibration/
validation sample”. Optional sample conditioning modules are
available to address natural gas streams that need additional
filtering and “speed loops” to reduce sample transport lag times.
Operator interface
Functional setup and operation of the NGC8206
is accomplished by using a graphical user’s interface software
package called PCCU 32 (supplied with each unit) operating on
a laptop PC in a Microsoft® Windows® environment. The
“Windows®” utilities, combined with software designed
specifically for the NGC8206, provide a powerful tool for
operations, diagnostics, and downstream data handling.
The PC can be directly connected to the NGC8206 via an
RS-232, USB, or Ethernet connection, or indirectly by remote
telemetry (phone modem, radio, cell phone, satellite, etc.).
The user is prompted through push-buttons, drop-down
boxes, wizards, and dialog boxes for setup, operations, data
collection and monitoring.
In addition, the unit has an optional ¼ VGA interactive display
screen allowing the user access to basic analysis data. The
user can also accomplish most of the “operator” functions
from the front panel display with out the use of a laptop PC.
The “Run-Hold-Calibrate” functions can be done via a magnet
interface through the explosion proof glass in the display.