OVERVIEW
The IR-S type infrared flame detector is an excellent high sensitivity type that
excels in “detection reliability”, “maintainability” and “economy”.
It supports boiler fuel diversity and low NOx (nitrogen oxide) operation.
By detecting the “average value” and “variation” of the infrared intensity of the
burner flame light transmitted to the infrared sensor (semiconductor element)
via a light guide (optical fiber), the detector can distinguish between the flame
and the light due to the furnace.
The detector distinguishes between flame and infrared light due to the red heat
of the furnace wall and detects flame fluctuations in the burner's ignition zone.
The IR-S type infrared flame detector has low brightness flame detection sensitivity
and a wide dynamic range, so it can be used for a variety of fuels such as natural
gas, heavy oil, and coal.

Features
• High sensitivity design
• High sensitivity to flame intensity enables stable detection of burner flames.
Flame is detected through unlit areas.
• Extended detection range
• With 100 times the dynamic range of conventional products, this sensor enables
stable detection of flames from slow burning to high intensity. No sensitivity
adjustment of the sensor is required in the field.
• Easy Maintenance
• A spherical lens is used to eliminate the need to clean the sensor window during
normal boiler operation.
• Long Life Sensor
• No periodic replacement is required due to the use of long-life infrared
semiconductor sensor elements.
• Fewer panels
The detector unit is compact and features a space-saving design that allows one
panel to cover up to 40 corners.
System Configuration
Flame Detector Panel
Flame detector main unit

For oil burners
The following examples apply to oil burners