Load Control
The load control uses digital signal processing techniques to provide significantly
improved accuracy and speed of response over conventional analog
measurement techniques. Accuracy is improved because the instantaneous
measurement of the voltage and current signal wave forms allows true RMS
measurement. Measuring true RMS power allows optimal load control in parallel
applications even in the presence of power line distortions. This method provides
faster response time because it eliminates the long integration times required in
analog circuits. Measurement speed is particularly important in power control
applications where rapid response to load and speed changes is essential.
Load control begins at breaker closure when the MSLC takes control of the
system load. The system load immediately prior to breaker closure is used as the
starting base load. On command, the adjustable ramp allows smooth, time
controlled loading into a set import/export level. A ramp pause switch is provided
to stop the ramp at any point.
The import/export control is an integrating control. It adjusts the percentage of
rated load carried by the individual generators, operating in isochronous load
sharing, in order to maintain a set import/export or base load level. The MSLC
will therefore maintain a constant base load or import/export level even with
changing utility frequencies. The MSLC provides switch inputs to allow raising or
lowering the internal digital base load or import/export reference. The control also
provides a 4–20 mA (1–5 Vdc) analog input for remote reference setting, if desired.
The MSLC is equipped with a Utility Unload switch, which provides an adjustable
time controlled ramp to lower the base load or import/export level. When the level
is below an adjustable threshold, the MSLC issues a breaker open command to
separate the utility from the local bus. Again, the ramp pause switch can be used
to stop the utility unload at any point. The maximum load that the MSLC can tell
the individual generators to carry is their rated loads. So, in the event that the
plant load is greater than the capacity of the operating generators, the utility
unload will stop when 100% rated load is reached on each of the operating
generators. This prevents accidental overloading of the local generators when a
reduced number are on line.
The MSLC also includes two adjustable load switches which can be used for
external functions or warnings when chosen system load levels are attained. The
high and low limit switches may also be activated when 100% or 0% base load
signal to the generators is reached.
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved