Var/PF Control
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The var/PF function controls the power factor on all of the DSLC-2 equipped machines operating in
isochronous load sharing. The PF control begins on breaker closure. The MSLC-2 has three modes of
Var/PF control (which are selected in Menu 4):
• Constant generator power factor – sets the power factor reference on all of the DSLC-2 con
trols to the internal reference chosen in the MSLC-2. The power factor can then be adjusted
using the voltage raise and lower inputs. The voltage raise command will make the power fac
tor more lagging. Conversely, the voltage lower command will make the power factor more leading.
• Utility tie power factor control – adjusts the power factor reference on all of the DSLC-2 con
trols in isochronous load sharing in order to maintain the power factor across the utility tie.
• Utility tie var control – adjusts the power factor reference on all of the DSLC-2 controls in
isochronous load sharing in order to maintain the level of vars being imported or exported from the utility.
The var/PF control mode begins with the load control mode selected. The constant generator power
factor and the utility tie power factor control can have the reference setting controlled by an analog in
put (see Menu 6). By closing the voltage raise and lower discrete inputs, you can select the analog re
mote input for reference control.