Description
• Overload protection – trip class 10A
• Phase loss sensitivity
• Disconnect function
• Temperature compensation from -25 … +50 °C
• Adjustable current setting for overload protection
• Suitable for three- and single-phase application
• Trip-free mechanism
• Clear switch position indication ON/OFF
Manual motor starters (also known
as motor protection circuit
breakers or manual motor
protectors) are electromechanical
protection devices for the main
circuit mainly used to switch
motors manually ON/OFF and
protect them fuseless against
short‑circuits, overloads and phase
failures. Fuseless protection with a
manual motor starter saves costs,
space and ensures a quick reaction
under short-circuit condition, by
switching off the motor within
milliseconds. Fuseless starter
combinations are setup together
with contactors.
Application
Manual motor starters (also known as motor
protection circuit breakers or manual motor
protectors) protect the load and the installation
against short-circuits and overloads. They are
three pole protection devices with thermal tripping
elements for overload protection and electromagnetic
tripping elements for short-circuit protection.
Furthermore, they provide a disconnect function for
safe isolation of the installation and the supply, and
they can be used for manual switching of loads.
Manual motor starters have a setting scale in amperes,
which allows direct adjusting of the device without any
additional calculation.
In compliance with international and national
standards, the setting current is the rated current of the
motor and not the tripping current.