Product Description
The VIM2 may be used for either DeltaV I/O simulation or
Ethernet I/O device integration. The VIM2 mounts on a
2-wide horizontal or 4-wide vertical carrier on either side
of the DeltaV controller. A dedicated DeltaV system power
supply is required.
IO Simulation
When used with DeltaV Mimic software, the VIM2
supports I/O simulation all DeltaV M-series I/O cards
including classic IO, FOUNDATION Fieldbus, Profibus DP,
DeviceNet, ASi-bus and Serial.
Mimic provides dynamic simulation for DeltaV system
software acceptance testing and operator training. Mimic
works by simulating the DeltaV I/O. It also simulates field
devices using Foundation Fieldbus, Profibus DP, DeviceNet,
and AS-i buses. For Mimic to do this, the physical I/O cards
are disconnected from the control system. The Mimic driver
writes to the I/O subsystem of the DeltaV controller. Process
models in Mimic simulate realistic process reactions to
control system output signals.
Each offline process controller uses one Mimic simulation
node and VIM. The I/O simulation driver is available with Mimic.
Ethernet I/O Integration
When used with the Ethernet I/O drivers, the VIM2
can communicate with high-speed Ethernet networks
over Modbus TCP, EtherNet/IP, FMC722. or PROFINET.
Depending on redundancy configuration of the VIM2. the
DeltaV controller auto-senses a commissioned VIM2 as four
or eight DeltaV I/O Cards.
• In simplex installations these cards will be sensed in slots 57-60 or 61-64.
• In dual simplex installations these cards will be sensed in slots 57 to 64.
• In redundant installations the redundant pairs will be sensed in slots 57 to 64.
Users configure the I/O signals for commissioned VIM2s
in DeltaV Explorer in the same manner as a DeltaV Serial, DeviceNet, or Profibus Card.