• Provides Automatic and Manual transfers of motor bus systems on Low
Voltage Switchgears in power plants and industrial processing plants to
ensure process continuity
• Automatically selects Fast, In-Phase, Residual Voltage, and Fixed
Time motor bus transfers, based on varying system conditions
• Applicable for one way and bi-directional Manual transfers
• Can be expanded to accommodate multiple breaker configurations
• Integrated control, supervisory functions, sequence of events, and
oscillograph recording in one device
• Extensive commissioning tools, including ringdown analysis

Standard Features
Automatic Transfer: The digital Motor Bus Transfer System (MBTS)
provides the following Automatic Transfer logic and features:
• Transfer initiated by protective relay external to the MBTS
• Automatic Transfer after a loss of the motor bus supply voltage
based on the programmable undervoltage element. This provides a
selectable backup feature if a protective relay transfer is not initiated.
• Fast Transfer with adjustable phase angle limit, delta voltage limit
and delta frequency limit
• In-Phase Transfer at the first phase coincidence if Fast Transfer is
not possible.
• Residual Voltage Transfer at an adjustable low residual voltage limit
if Fast Transfer is not possible
• Fixed Time Transfer after an adjustable time delay
• Programmable load shedding prior to initiating In‑Phase Residual
Voltage Transfer and Fixed Time Transfer
• Verify the new source (the source to which the bus is being
transferred) is healthy and within acceptable upper and lower voltage
limits
Manual Transfer: When a Manual Transfer is initiated the digital MBTS
provides the following:
• Sync check functions with adjustable parameters
• Hot Parallel Transfer if enabled (make‑before break)
• Fast Transfer, In‑Phase Transfer and Residual Voltage Transfer (if the
Hot Parallel Transfer is disabled)
• Programmable load shedding prior to initiating Residual Voltage
Transfer
• Verify the new source (the source to which the bus is being
transferred) is healthy and within acceptable upper and lower voltage
limits
Circuit Breaker Control: The digital Motor Bus Transfer System includes
the following Circuit Breaker
Control features:
• Control of two circuit breakers with two individual programmable
breaker closing times
• Three-breaker configuration can be provided by two M‑4172 devices
• Breaker status supervision
• Breaker failure monitoring
Additional Standard Features
• Sequential or Simultaneous Transfer Mode
• Bus Phase Undervoltage (27B)
• Frequency (81) and Rate of Change of Frequency (81R) for load
shedding
• Breaker Failure Source 1 and Source 2
• Bus VT Fuse‑Loss Detection (60FL)
• Auto Trip
• Auto Close
• Four dry output contacts (two trip and two close) for Source 1 and
Source 2. one lockout/ blocking output contact, and 3 programmable
output contacts (2 Form "a" and one Form "c")
• Two Breaker Status 52b (or 52a) inputs for the Source 1 and Source
2 breakers, four programmable digital inputs
• All functions can be enabled or disabled
• Remote/Local control selection
• Device ON/OFF Control Selection
• M‑3931 Human‑Machine Interface (HMI) Module
• M‑3976 Status Module
• IRIG‑B time synchronization
• Oscillographic recording
• Two RS‑232 ports (front and rear) and one RS‑485 port* (rear)
*When using M‑3871 ISScom V10.02.XX to communicate with M‑4172
units with Firmware version V03.00.XX and higher, the RS‑485 port
(COM 3) is not available.
• S‑4200 or M‑3871 ISScom® Communications and Oscillographic
Analysis Software
Optional Features
• 5 A or 1 A models available
• 60 Hz or 50 Hz models available
• Available in vertical panel mount
• Redundant Power Supply
• External TCM and CCM available
• Ethernet port RJ‑45 10/100 Base‑T (MODBUS over TCP/IP)
• Ethernet port RJ‑45 10/100 Base‑T (IEC 61850 Protocol)