Adapts M‑2001 Series Digital Tapchanger Control to Solid‑State Controls
for Howard Industries SVR‑1
• Provides built-in CT shorting protection when the M-2001 Series Digital
Tapchanger Control is removed
• Optional SCADA Cutout (Local/Remote) switch (for use with SCADA
enabled M-2001C controls) allows Local Blocking of SCADA commands
• Optional SCAMPTM (SCADA Controllable Auto/Manual Pushbutton)
switch replaces AUTO/OFF/MANUAL toggle switch
• Optional 2 Level Local Voltage Reduction switch
The M‑2302 is an adapter panel which, when combined with the M‑2001
Series Digital Tapchanger Control, provides convenient direct replacement
of Howard Industries SVR‑1 solid‑state controls. The M‑2302 consists of
a front panel with hinge leaves, and mounts into the control cabinet using
the same two hinge pins which must be saved from the original control.

Interface
External connections are made using a wiring harness that connects from
a sixteen‑position terminal block to the terminal block on the existing control
cabinet. An additional terminal block provides auxiliary functions, including
self‑test alarm, user‑programmable alarm, auto disable and manual raise/lower.
Features
Separate fuses for test terminal, voltage sensing and motor power are on
the front panel, and spare fuses for each are located in the fuse holder.
Binding posts on the front panel allow easy connections for test procedures.
RAISE/OFF/LOWER, AUTO/OFF/MANUAL and VOLTAGE SOURCE switches,
DRAG HANDS RESET pushbutton, and NEUTRAL LIGHT are standard.
AUTO/OFF/MANUAL switch may be configured for switch status detection.
NEUTRAL LIGHT will light to indicate that the regulator is in the neutral
position, for those regulators equipped with a circuit for this purpose.
Options
SCADA CUTOUT switch allows Local blocking of SCADA commands (for use
with SCADA enabled M‑2001C controls). The SCADA Cutout switch must
be used with a M-2001 Series Control with firmware version D‑0146V08.01.22
or later installed.
SCAMPTM (SCADA Controllable Auto/Manual Pushbutton) switch allows the
Auto/Manual state on the adapter panel to be changed by a SCADA command.
The SCAMP pushbutton switch must be used with a M‑2001 Series Control
with firmware version D-0146V08.05.XX or later installed.
Voltage Reduction switch allows 2 levels of Voltage Reduction to be selected.
Testing Specifications
High Voltage: All input and output terminals will withstand 1500 Vac rms to
chassis or instrument ground for one minute with a leakage current not to
exceed 25 mA, for all terminals to ground. Input and output circuits are
electrically isolated from each other, from other circuits and from ground.
Surge Withstand Capability: All input and output circuits are protected against
system transients. Units pass all requirements of ANSI/IEEE C.37.90.1-1989
defining surge withstand capability.
Radiated Electromagnetic Withstand Capability: All units are protected against
electromagnetic radiated interference from portable communications transceivers.
Environmental
Temperature Range: Functionality is maintained from -40° to +85° C.
Humidity: Functionality is maintained under 95% relative humidity (non-condensing).
Fungus Resistance: A conformal printed circuit board coating inhibits fungal growth.
Physical
M‑2302 Adapter Panel – Specification
Size with M‑2001 Series Digital Tapchanger Control: 16.00" high x 9.50"
wide x 4.185" deep (40.6 cm x 24.13 cm x 10.5 cm)
Approximate Weight: 2 lbs, 7 oz (1.11 kg)
Approximate Shipping Weight: 5 lbs, 7 oz (2.47 kg)
Approximate Weight with M‑2001 Series Digital Tapchanger Control: 6 lbs, 2 oz (2.78 kg)
Approximate Shipping Weight with M‑2001 Series Digital Tapchanger Control: 11 lbs, 2 oz (5.05 kg)
Warranty
The M-2302 Adapter Panel is covered by a five year warranty from date of shipment.
wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com