The M‑2069 Adapter Panel, when combined with the M‑2001C or M-2001D Digital Tapchanger
Control, offers convenient, direct replacement of Westinghouse SVC or SVR controls and
Beckwith Electric M‑0067E controls or M-2067B adapter panels.
The M‑2069-M-2001D combination can also be used as a general purpose LTC transformer control.
The M‑2069 enables changing of the M‑2001 control without adapter panel removal or rewiring.

• Connects easily to the M‑2001 Series Digital Tapchanger Control using four mounting screws
and 24-pin connector
• Provides mounting adaptable to several different configurations
• Provides built-in CT shorting protection when the M‑2001 Series Tapchanger Control is removed
• SCADA Cutout (Local/Remote) switch allows Local Blocking of SCADA commands (for use with
SCADA enabled M-2001C and D controls)
• Convenient Auto/Off/Manual and Raise/Lower Switches for toggling between Automatic mode
and Manual (local) mode to adjust the tapchanger position from the front panel
The M‑2069 is an adapter panel which, when combined with the M‑2001C or M‑2001D Digital
Tapchanger Control, provides convenient direct replacement for Westinghouse SVC and SVR
controls and Beckwith Electric M‑0067E controls. The M‑2069 can also be used, with the M‑2001
Series Tapchanger Control, as a general purpose LTC transformer control. The M‑2069 permits
changing of the M‑2001 control without adapter panel removal or rewiring.
Interface
External connections are made to two terminal blocks located on the rear of the adapter panel.
The second terminal block provides auxiliary functions, including self‑test alarm, user‑programmable
alarm, manual raise/lower, operations counter and ∆VAr 2 disable.
Front Panel Controls
AUTO/OFF/MANUAL: toggles between Auto operation of the control and Manual operation that
enables tapchanger adjustment from the front panel using the Raise/Lower toggle switch.
RAISE/LOWER: allows local manual Raise and Lower commands to be initiated in Manual mode.
LOCAL/REMOTE (SCADA CUTOUT): allows Local blocking of SCADA commands.
Testing Specifications
High Voltage: All input and output terminals will withstand 1500 Vac RMS to chassis or instrument
ground for one minute with a leakage current not to exceed 25 mA, for all terminals to ground. Input
and output circuits are electrically isolated from each other, from other circuits, and from ground.
Surge Withstand Capability: All input and output circuits are protected against system transients.
Units pass all requirements of ANSI/IEEE C.37.90.1‑1989 defining surge withstand capability.
Radiated Electromagnetic Withstand Capability: All units are protected against electromagnetic
radiated interference from portable communications transceivers.
Control Accuracy Specification: All units comply with ANSI/IEEE C57.15‑1986 defining control
accuracy of operation.
Environmental
Temperature Range: Functionality is maintained from ‑40° to +85° C.
Humidity: Functionality is maintained under 95% relative humidity (non‑condensing).
Fungus Resistance: A conformal printed circuit board coating inhibits fungus growth.