• Provides 24 Vdc power to any Beckwith Electric M-7600 Series
Protection System or Control configured with Low Voltage power supply
• Provides 13.8 Vdc Accessory power
• Accepts AC or DC power input from 105 to 285 Vac (50/60 Hz) or 120
to 285 Vdc
• Charges a 24 Vdc battery system which upon AC power interruption
can be used as temporary power (UPS) supply
• Transient protected
• Substation hardened -40° C to +85° C
• Conformal coated

Introduction
The M‑2032B Battery Charger/Power Supply provides 24 Vdc output to power
the low voltage configured M‑7600 series of Beckwith Electric Protection and
Control Systems. Also provided is a 13.8 Vdc output which can be used to
power radios or other auxiliary equipment.
In addition to providing output power, the M‑2032B is capable of charging 24
Vdc batteries when main power is supplied. Included is circuitry to detect a
loss of main power and automatically provide backup power from the 24 Vdc
batteries ensuring operation is not interrupted.
Stand Alone Applications
In a stand alone application the M‑2032B is designed to provide the following
features:
• 24 Vdc Output
• 13.8 Vdc Output
• 24 Vdc Battery Charging
• Circuitry to detect a loss of main power and automatically provide backup power
from the 24 Vdc batteries ensuring operation is not interrupted.
• When running on the 24 Vdc batteries the M‑2032B will shut down if the battery
voltage drops below 19 Vdc.
The M‑2032B is intended for indoor use or mounted inside a chassis or enclosure
only.
Battery Charging Features
The M‑2032B is designed to charge a 24 V sealed lead‑acid battery. It includes an
internal circuit to prevent overcharging of the batteries and extend their life.
• Tri‑Level Bulk/Absorption/Float Charger with Pre‑Charge
• When battery voltage is below 21 Vdc the charge current is limited to 40 mAdc
(Pre‑Charge), once the battery voltage is greater than 21 Vdc, the charger will begin
charging at the higher rates (Bulk/ Absorption/Float).
This prevents high current in a damaged battery. The Bulk mode charges the battery
at a rate that minimizes charge time and maximizes battery capacity. The Float mode
maintains the battery charge after the Bulk mode charge has finished, preventing
overcharging of the battery.
• The battery charge voltage is temperature compensated to optimize battery
charge and life.
M‑7600 Series Protection and Control System Applications
The M‑2032B in conjunction with the M‑7600 Series includes smart battery charging
features that are a result of the Beckwith Electric proprietary communication protocols
employed between the M‑2032B and M‑7600 Series utilizing a SATA cable connected
via the Aux I/O port on the M‑7600 Series. The following features are provided when
a M‑2032B is connected to a M‑7600 Series:
• Receives commands to:– Turn‑on/off battery test load– Turn‑on/off 13.8 Vdc
accessory supply– Turn battery supply off
• Communicates the following to the M‑7600 Series:
– Charger state
– Main power supply status
– Battery Voltage
– Battery Current
– Recloser Gas Pressure (if recloser is equipped with sensor)
• Includes a Wakeup system that is initiated by the local panel pushbutton.
Turn-on/off Battery Load Test Command
M‑2032B Battery Charger/Power Supply – Specification
The M‑7600 Series issues the "Turn‑on/off Battery Load Test" command to the
M‑2032B to test the battery capacity when the unit is operating from the main
power supply.
Turn-on/off 13.8 Vdc Accessory Supply (Aux Power)
The accessory supply provides power for external devices such as radio,
modems, etc. When the M‑2032B is used in conjunction with the M‑7600
Series, the 13.8 Vdc output can be enabled/disabled utilizing the control's
HMI, IPScom, or communication protocols.
Turn Battery Supply Off Command
When the battery voltage decreases to less than a level set by the user, the
battery supply to the M‑7600 Series will be turned off (Sleep Mode) to protect
the battery. Discharging batteries below certain levels will shorten the life of
or damage the battery.
Wakeup System Command
The Wakeup system command is initiated by the M‑2032B local panel pushbutton.
The wakeup system command allows the user to wake the M‑7600 Series from
the Sleep Mode that was initiated by the Battery Supply Off command.
The wakeup system command restores power to the unit for a user defined time
period. If the main source power is not restored, then the Turn Battery Supply
Off command will be reinstated placing the M‑7600 Series in Sleep Mode.
Battery Charger Monitoring System
The Battery Charger Monitoring System must be enabled in the Setpoints/Common
Setpoints/PSBC/IED Power Supply/Battery Charger Monitor dialog screen (Figure 1).
Also included in the Battery Charger section are the settings for:
• Minimum battery voltage to turn OFF IED
• Enable/Disable and set time to perform Load Test
• Power Off Delay After AC Loss
• Power Off Delay After Wakeup
• Enable/Disable 13.8 Vdc Accessory Supply (Aux Power)
wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com