• Maintains the M-2001C/D or M-6200 energized during power outages to
maintain the continuity of the communications loop
• Accepts power input from station auxiliary supply over a range of 105
Vac to 140 Vac (50 or 60 Hz)
• Fuse protected and transient suppressed, input and output
• Substation hardened -40° C to +85° C
• Conformal coated
• Includes 6 foot output cable and adapters for M-2001C/D and M-6200
controls

Input
105 Vac to 140 Vac at 50Hz/60Hz
Burden of less than 2 VA
Fuse protected (1.5 A)
Transient protected
Output
+12 Vdc nominal @ 1 amp
Fuse protected (1.5 A)
Transient protected
Transient Protection
Surge Withstand Capability:
IEEE C37.90.0-2002: 2500 V pk-pk oscillatory, 4000 V pk fast transient burst
IEEE C37.90.0-2002: 2500 V pk-pk oscillatory, 5000 V pk fast transient burst
High Voltage: All M-2027 input and output terminals will withstand 1500 Vac
RMS to chassis or instrument ground for one minute with a leakage current
not to exceed 25 mA, for all terminals to ground. Input and output circuits are
electrically isolated from each other, from other circuits and from grounds.
Radiated Electromagnetic Withstand Capability: All units are protected against
electromagnetic radiated interference from portable communications transceivers.
Environmental
Temperature range: -40° C to +85° C
Humidity: Operational to a maximum of 95% relative humidity.
Fungus resistance: A conformal coating is used on the printed circuit board
coating inhibit fungus growth.
Physical
Size: 7.32" long x 4.10" wide x 2.40" high (18.6 cm x 10.2 cm x 6.1 cm)
Approximate Weight: 2.0 lbs (.91kg)
Warranty
The M‑2027 is covered by a five year warranty from date of shipment.