• Maintains the M-2001C/D or M-6200 energized during power outages
to maintain continuity The Communications Loop
• Accepts AC and/or DC power input (50 or 60 Hz) from auxiliary station
supply over the following ranges:
21 to 32V DC
42 to 60V DC
105 to 145V AC/DC
• Fuse protected and transient suppressed, input and output
• Substation hardened -40° C to +85° C
• Conformal coated
• Includes 6 foot output cable and adapters for M-2001C/D and M-6200
controls

Inputs (AC and/or DC)
21 to 32 Vdc
42 to 60 Vdc
105 to 145 V AC/DC
Load of less than 8 VA
Bipolar Fuse protection (1.5 A)
Reverse polarity protection for a dc input
Transient protected
Output
+12 Vdc regulated (± .5 V) @ 1.5 amp
Transient protected
Transient Protection
Surge Withstand Capability:
IEEE C37.90.0-2002: 2500 V pk-pk oscillator, 4000 V pk fast transient burst
IEEE C37.90.0-2002: 2500 V pk-pk oscillator, 5000 V pk fast transient burst
High Voltage: All M-2026 input terminals will withstand 1500 Vac RMS to
chassis or instrument ground for one minute with a leakage current not to
exceed 25 mA, for all terminals to ground. The M-2026 output terminals will
withstand 500 Vac RMS to chassis or instrument ground for one minute with
a leakage current not to exceed 25 mA, for terminals to ground.
Input and output circuits are electrically isolated from each other, from other
circuits and from ground.
Radiated Electromagnetic Withstand Capability: All units are protected against
electromagnetic radiated interference from portable communications transceivers.
Environmental
Temperature range: -40° C to +85° C
Humidity: Operational to a maximum of 95% relative humidity.
Fungus Resistance: A conformal printed circuit board coating inhibits fungus
growth.
Physical
Size: 12.0" long x 4.10" wide x 2.38" high
Approximate Weight: 3.0 lbs (1.36 kg)
Warranty
The M-2026 is covered by a five-year warranty from the date of shipment.