The LS 4 is an intelligent synchronizer and protection device capable of
measuring voltage and current though integrated measuring inputs.
It can calculate set point values using internal software routines (i.e.
for synchronization) and can transfer these set point values to a lower
level GCP control unit using the integrated CAN bus (Guidance Level).
The LS 4 is also capable of closing the connected breaker at the
synchronous point. Additionally the measured/calculated values may
be monitored for exceeding/falling below a predefined set point result
ing in an automatic opening of the connected circuit breaker.

Electrostatic Discharge Awareness
All electronic equipment is static-sensitive, some components more than
others. To protect these components from static damage, you must take
special precautions to minimize or eliminate electrostatic discharges.
Follow these precautions when working with or near the control.
1.) Before doing maintenance on the electronic control, discharge the
static electricity on your body to ground by touching and holding a
grounded metal object (pipes, cabinets, equipment, etc.).
2.) Avoid the build-up of static electricity on your body by not wearing
clothing made of synthetic materials.
Wear cotton or cotton-blend materials as much as possible because these
do not store static electric charges as easily as synthetics.
3.) Keep plastic, vinyl, and Styrofoam materials (such as plastic or
Styrofoam cups, cigarette packages, cello phane wrappers, vinyl books or
folders, plastic bottles, etc.) away from the control, modules, and work
area as much as possible.
4.) Opening the control cover may void the unit warranty.
Do not remove the printed circuit board (PCB) from the control cabinet
unless absolutely necessary. If you must remove the PCB from the control
cabinet, follow these precautions:
• Ensure that the device is completely voltage-free (all connectors have to
be disconnected).
• Do not touch any part of the PCB except the edges.
• Do not touch the electrical conductors, connectors, or components with
conductive devices or with bare hands.
• When replacing a PCB, keep the new PCB in the plastic antistatic protective
bag it comes in until you are ready to install it. Immediately after removing
the old PCB from the control cabinet, place it in the antistatic protective bag.
Functional Description
Introduction
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Measuring Values
• Voltage
Three-phase measurement of the rms values of the phase-to-neutral and
phase-to-phase voltages of two systems (system [A] and [B]; system [B]
only phase-to-phase). This unit can be delivered with the following measuring
voltage ranges (rated values). Selection of type during ordering:
- 66/115 Vac - 230/400 Vac
• Frequency
Time measurement from the digitally filtered measuring voltages. The
measurement of the frequency is three phased if all voltages are greater
than 15 % of the rated value (100 Vac or 400 Vac). This guarantees a fast
and precise measurement of the frequency. However the frequency is still
measured correctly even if voltage is only applied to one phase.
• Current
Three-phase rms values.
• Real power
Single-phase measuring calculated from apparent power and power factor
cosphi (power factor).
• Re-active power
Single-phase measurement calculated from apparent power and power factor
sinphi.
• Power factor cosphi
Time measurement between the filtered measuring values of the voltage VL12
and the conductor current IL1.
General Functions
• 1 freely configurable relay output (NO) as ready for operation relay
• 4 freely configurable relay outputs (NO)
• 2 freely configurable relay outputs (change-over)
• 1 relay output (change-over) for synchronization (pulse relay)
• Discrete input for alarm blocking or acknowledgment
• Password system
• CAN bus interface
• 4 discrete control inputs
Control/Synchronization Functions
• Transmission of set point values via CAN bus to a lower level control unit
(i.e. GCP-31) for synchronization
of one circuit breaker with voltage and frequency adjustment
• Transmission of actual values via the CAN bus to a control unit (i.e. GCP-31)
for real power control
• Closing of the CB onto a dead (de-energized) bus bar
Power Factor Definition
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The phasor diagram is used from the generator's view. This defines the following
definitions.
Power Factor is defined as a ratio of the real power to apparent power. In a purely
resistive circuit, the voltage and current waveforms are instep resulting in a ratio
or power factor of 1.00 (often referred to as unity). In an in ductive circuit the
current lags behind the voltage waveform resulting in usable power (real power)
and unusable power (reactive power). This results in a positive ratio or lagging
power factor (i.e. 0.85lagging). In a capacitive circuit the current waveform leads
the voltage waveform resulting in usable power (real power) and unusable power
(reactive power). This results in a negative ratio or a leading power factor (i.e.
0.85leading).
Function
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Synchronizing
The variable system is synchronized to the fixed system (variable and fixed system
can be configured) for voltage and frequency. This is done by sending set point
values through the CAN bus to the lower level GCP control that are electrically
connected with the configured variable system. The LS 4 calculates the correct
synchronous point to issue a CB close command using the switching time of the
CB (Parameter 37). Synchronizing/closing of the CB is done if the following
conditions are fulfilled simultaneously:
• The unit is in automatic mode.
• The synchronizing function is enabled (Parameter 31).
• Voltage and frequency of both systems [A] and [B] are within the configured
range (for both systems this range is adjustable by changing the settings for the
voltage monitoring functions of system [A] if this protection is enabled;
Dead Bus Start
A close CB command without synchronization may be issued if the following
conditions are fulfilled simulta neously:
• Dead bus start function is configured to ON (Parameter 43).
• Discrete input "Enable CB" is set.
• Discrete input "Reply: CB is open" is set.
• One of the three possible black start functions is enabled
1.) Parameter 46 (Vsystem A=Vn/Vsystem B=0)
Vsystem A is equal with Vn (using the configured rated voltage difference dV
|V-Vn|) and Vsystem B is zero (using the configured zero voltage difference
dV |V-0|).
2.) Parameter 45 (Vsystem A=0/Vsystem B=Vn)
Vsystem A is zero (using the configured zero voltage difference Vd |V-0|) and
Vsystem B is equal with Vn (us
ing the configured rated voltage difference dV |V-Vn|).
3.) Parameter 44 (Vsystem A=0/Vsystem B=0)
VA is zero and VB is zero (using the configured zero voltage difference dV |V-0|).
• No alarm is triggered if parameter "Blocking at dead start alarm" is configured
to ON (Parameter 51).
• No GCP is trying to carry out a dead bus start.
• No higher prioritized LS 4 is trying to close its breaker.

wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com
Copyright © 2009 - 2026 Cld , All Rights Reserved K-JIANG All rights reserved