The Traditional I/O subsystem includes:
• I/O interface carrier (a DIN rail surface mounted)
on which all I/O related components are installed.
• Bulk AC to 24V DC power supply for field devices.
An I/O interface consisting of an I/O card and an
I/O terminal block.
• A variety of analog and discrete I/O cards enclosed
in a common form factor that easily plugs into the
I/O interface carrier.
• A variety of I/O terminal blocks mounted on the I/O interface
carrier that can be pre-wired before I/O card installation.
I/O Cards
A variety of analog and discrete I/O cards are available to meet
your specific requirements. The following cards support simplex
or redundant installation:
• AI 4-20 mA HART 8 channels
• AO-4-20 mA HART 8 channels
• DI, 24V DC Dry Contact, 8 channels
• DO 24V DC High-Side, 8 channels
• AI (Plus) 4-20 mA HART, 16 channels
• AO (Plus) 4-20 mA HART, 16 channels
• DI (Plus) 24V DC, Dry Contact, 32 channels
• DO (Plus) 24V DC, High-Side, 32 channels
The following I/O cards are supported in simplex format
to meet your field wiring needs.
• AI Isolated, 4 channels
• RTD, 8-channels
• Thermocouple, 8 channels
• Millivolt, 8 channels
• DI, High Density, 32 channels
• DI 24V DC Isolated, 8 channels
• Multi-Function, 4 channels (Isolated DI)
• Sequence of Event, 16 channels (DI 24 V DC)
• DI 120V AC Low Side Detection, 8 channels
• DI 120V AC Isolated, 8 channels
• DO 24V DC Isolated, 8 channels
• DO 120/230V AC High-Side, 8 channels
• DO 120/230 Isolated, 8 channels
All I/O cards are enclosed in a common form factor that plugs
into the I/O interface carrier. The housing is clearly labeled with
the enclosed I/O card type. All cards have power and internal
error indicators. Eight-channel cards have clearly visible channel status LEDs.
All cards meet ISA G3 corrosion specifications by the careful
selection of superior electronic components and the use of conformal coating.
Pulse Counters are available on most DI cards. The supported
maximum frequency varies from 0.1 Hz on AC signals to
75 or 120 Hz on 24V DC inputs. For higher pulse counts,
up to 50 KHz, use the Multi-Function card’s high speed pulse input.
The DeltaV system provides control module level time
stamping for log events and alarms. For greater event
resolution, the 16-channel Sequence-of-Events DI card
can provide signal driven events to a resolution of +/- 0.25 ms
per card, or within 1 ms per controller. Please refer to
the Sequence-of-Events PDS for more information on
Sequence-of-Event data collection and system options for this feature.
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved