INIIT12 INFI-NET to INFI-NET Transfer Module
The NIS module works in conjunction with the INFI-NET to
INFI-NET transfer modules. This allows any node to communi
cate with any other node within the INFI-NET system.
The NIS module is a single printed circuit board that occupies
one slot in the module mounting unit (MMU). The circuit board
contains microprocessor based communication circuitry that
enables it to interface with the INFI-NET to INFI-NET transfer
modules via the I/O expander bus. Both the INFI-NET to
INFI-NET interfaces require a specific interface module and an
NIS module (the INIIL02 module requires two NIS modules).
Two captive latches on the front-mounted faceplate secure the
module to the MMU card cage. There are 16 LEDs on the face
plate that display error codes or event/error counts.
Each NIS module connects to its INFI-NET communication
loop by a cable connected to an NTCL01 Communication Ter
mination Unit or NICL01 Communication Termination Module.
Communication between nodes is through coax or twinax
cables that connect the termination units or modules on each
node. Power and I/O expander bus connections follow the
same connector assignments common to most INFI 90 OPEN
modules (P1 for power, P2 for I/O expander bus).
The INIIT12 INFI-NET to INFI-NET Transfer Module supports
bidirectional communication through two RS-232-C ports. Port
one passes system data only. Port two passes system data or
can be used as a diagnostic port. The central INIIT12 module
can use a variety of means to link to the satellite INIIT12 mod
ule such as modems, microwave and transceivers. The INIIT12
module communicates directly with an NIS module through
the I/O expander bus.
The INIIT12 module is a single printed circuit board that occu
pies one slot in the module mounting unit, adjacent to its NIS
module. The circuit board contains the serial communication
circuitry necessary for it to communicate with another INIIT12 module.
Two captive latches on the INIIT12 faceplate secure the module
in the MMU card cage. The faceplate contains eight CPU LEDs,
a red/green status LED, and a stop/reset switch.
Interface termination is through a cable connection between
P3 of the INIIT12 module and an NTMP01 Multi-Function Pro
cessor Termination Unit or NIMP01 Multi-Function Processor
Termination Module. INIIT12 module power and I/O expander
bus connections follow the same connector assignments com
mon to most INFI 90 OPEN modules (P1 for power, P2 for I/O expander bus).