The dc output from the transducer, used to sense the generator voltage, is applied to this input. This
signal is used for generator voltage metering if the external generator voltage sensing mode is selected.
Gate Drive Block (BL+, BL–)
When a contact closure is sensed at this input, SCR firing is blocked and the IFM-150 output is disabled.
Full Invert (INV+, INV–)
The pulse outputs are forced to their maximum delay when a contact closure is sensed at this input. This
results in maximum negative voltage at the exciter output until the field current decays to nearly zero. The
Full Invert contact input is used only on full-control bridges.
Start/Stop (FS+, FS–)
A contact closure at this input initiates sampling of the synchronizing voltage (to determine phase
rotation) and calculation of the pulse generation time delay. Opening this contact input terminates the
firing pulses.
Terminal Voltage Limiter Enable (VTLIM+, VTLIM–)
The terminal voltage limiter is enabled when contact closure is sensed at this input. When enabled, the
terminal limiter will prevent the generator voltage from exceeding the limiter reference level.
Outputs
The following paragraphs describe the function of the IFM-150 outputs.
Firing Pulses
These outputs supply firing pulses to the gate trigger inputs of the Rectifier Chassis. The firing pulse
terminals used depend on the model of IFM-150. Installation illustrates typical firing pulse output
connections for single-phase and three-phase rectifier chassis applications.
Watchdog Relay (WTCHDG1. WTCHDG2)
The Watchdog Relay output closes to indicate a software execution problem within the IFM-150 or a loss
of power supply. This output remains closed for several seconds after the application of control power.
Alarm Relay (ALRM1. ALRM2)
The Alarm Relay output closes when the monitored synchronizing transformer frequency decreases
below the programmable level of the BESTCOMS Safe Mode Frequency setting. The output opens when
the frequency increases to 1 hertz above the Safe Mode Frequency setting. This output is disabled when
the Start/Stop contact input (FS+, FS–) is open.
Terminal Voltage Limiter Active Relay (LIMACTV1. LIMACTV2)
The normally-open Terminal Voltage Limiter Active Relay output closes when the terminal voltage limiter
activates due to high generator voltage. When the generator voltage decreases below the limiter
reference level, the terminal voltage limiter deactivates and the Terminal Voltage Limiter Active Relay
output opens.