DESCRIPTION
BE1-87T Transformer Differential Relays provide primary protection for power transformers and are
available in either Single-Phase or Three-Phase configurations. The solid-state BE1-87T compares the
currents entering and leaving the protected transformer. If a fault is detected, the relay initiates a trip
signal to isolate the power transformer. This limits damage to the transformer and minimizes the impact
on the power system.
BE1-87T relays use three types of restraint:
• Percentage of through-current
• Second harmonic
• Fifth harmonic

Selectivity in differential relaying is based on the ability to distinguish between internal and external faults.
This is achieved by comparing the currents into and out of a power transformer. Comparing these
currents often requires more than two inputs. For example:
• Power transformers may have a significant portion (greater than 10 %) of the current flowing in a
third or tertiary winding.
• Power transformers can have multiple breakers for a given winding (e.g., ring bus or breaker
and-a-half bus).
BE1-87T relays are available with up to five restraint inputs for the single-phase unit and up to three
restraint inputs per phase for the three-phase unit.
APPLICATION
In general, power transformers have different values of current flowing through their primary, secondary,
and tertiary windings. These currents have specific phase relationships depending upon the connections
of the individual windings (e.g., wye/delta). As inputs to a differential relay, these currents must be
compensated or scaled so that the relay can compare the inputs and determine when an unbalance
exists. Under ideal operating conditions, the scaled vector sum of these currents is zero.
Because it is practically impossible to match the magnitudes of these detected currents from the various
power windings using standard CT ratios, the currents are matched within the relay by scaling each of the
applied currents by an appropriate factor called a Tap Setting. This is set by means of the front panel
INPUT dials. By selecting suitable tap ratios, the applied currents are scaled within the relay to achieve
the desired balance for normal operating conditions. BE1-87T relays offer a range of available tap settings
for inputs between 0.4 A to 1.78 A (Sensing Input Range Options 2 and 4 for a 1 A CT) or 2.0 to 8.9 A
(Sensing Input Range Options 1 and 3 for a 5 A CT). These settings are independently adjustable in
increments of 0.02 A for Sensing Input Range Options 2 and 4. or 0.1 A for Sensing Input Range Options
1 and 3. These small increments allow more precise scaling of the applied currents and usually eliminate
the need for installing auxiliary ratio-matching CTs.
Single-Phase
BE1-87T Single-Phase relays require phase angle compensation to be accomplished externally by proper
connection of the system CT secondaries. A wye/delta transformer requires that the CT secondaries be
connected in delta for the wye winding and in wye for the delta winding. This type of connection also
eliminates the zero-sequence component of current which could cause a false trip (operation) during
external ground fault conditions on the wye system.
Three-Phase
BE1-87T Three-Phase relays can provide zero-sequence filtering and compensation for phase shifts
introduced by the connections of the power transformer. This 30° Phase Shift compensation (either ±30°
or no compensation) is field selectable. Additionally, this feature allows sharing the transformer differential
relay CTs with other relays or instrumentation.
BE1-87T relays use the highest input current (in per unit values) to operate on maximum restraint. The
relay does not have a conventional operate winding in the internal magnetics. Operating current is
developed within the electronics of the relay.
Percentage Restraint
A primary concern in differential relay applications is security against high current levels caused by faults
outside the protected zone. Inevitable differences in the saturation characteristics between current
transformers require a compensating decrease in relay sensitivity. It is also necessary to be able to adjust
wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com