The 48 VDC Positive/Negative Input Module (IC670MDL641) provides a single group of 16 discrete inputs, which may be driven by positive or negative logic.
Power Sources
The module receives power from the Bus Interface Unit for its own operation. An external 48
VDC supply is needed to power the input devices.
LEDs
Individual LEDs (logic side), visible through the transparent portion of the module top,
indicate the On/Off status of each input. The PWR LED is On when field and backplane
power are present.
Host Interface
Intelligent processing for this module is performed by the Bus Interface Unit or elsewhere in
the system. This includes configuring features such as input defaults and fault reporting.
The module has 16 bits (two bytes) of discrete input data. A Bus Interface Unit is required
to provide this input data to the host and/or local processor.
Module Operation
A network of resistors, capacitors, and zener diodes establishes input thresholds and provides
input filtering. Optoisolators provide isolation between the field inputs and the module’s logic
components. An oscillator and switch form a sampling circuit that is transparent to the
controller and the LEDs that indicate the state of the inputs. Data from all 16 inputs is placed
into a data buffer. The module’s circuit LEDs show the current states of the 16 inputs in this
data buffer.
Parallel-to-serial converters change input data from the data buffer into the serial format
needed by the Bus Interface Unit.
After checking the Board ID and verifying that the module is receiving appropriate logic power
from the Bus Interface Unit (which is reflected by the state of the module’s Power LED), the Bus
Interface Module then reads the filtered, converted input data.
Positive or Negative Inputs
Inputs for this module can be either positive or negative (all 16 inputs must be the same type).
Both types of signal produce a logic 1 (true) when the switch is closed. Selection of positive or
negative operation is made by the manner in which the external power supply is connected to
the inputs and to the I/O Terminal Block.
Positive inputs receive current from input devices and supply current to the common or
negative power bus. Input devices are connected between the positive power bus and the input
terminals.
Negative inputs provide current to input devices and accept current from the common or
positive power bus. Input devices are connected between the negative power bus and the input
terminal.
Field Wiring
The following illustration shows terminal assignments for the 48 VDC Positive/Negative
Input Module.
Connection to the A terminals is optional. They can be used as shown on the next page.
The Terminal Block with box terminals has 25 terminals for each module, each of which
accommodates one AWG #14 (avg 2.1mm2 cross section) to AWG #22 (avg 0.36mm2 cross
section) wire, or two wires up to AWG #18 (avg. 0.86mm2 cross section). When an external
jumper is used, the wire capacity is reduced from AWG #14 (2.10mm2) to AWG #16
(1.32mm2).
The I/O Terminal Block with barrier terminals has 18 terminals per module. Each terminal
can accommodate one or two wires up to AWG #14 (avg 2.1mm2 cross section).
The I/O Terminal Block with Connectors has one 20-pin male connector per module. The
mating connector is Amp part number 178289–8. Any tin-plated contact in the AMP D–3000
series can be used with the connector (Amp part number 1–175217–5 for high contact force
receptacle for 20–24 gauge (0.20–0.56mm2) wires), 1–175218–5 for high contact force
receptacle for 16–20 gauge (0.56–1.42mm2)).
Wiring Examples with Auxiliary Terminal Blocks
If the module is installed on an I/O Terminal Block with Box Terminals or an I/O Terminal
Block with Barrier Terminals, an Auxiliary Terminal Block may be required to provide
additional wiring terminals. For the I/O Terminal Block with Wire to Board Connectors,
external connection points are usually be preferred, although an Auxiliary Terminal Block
can be used..