540CID01: Base Module
DIN rail mounted base module RTU540:
4x serial ports (RS-232. RS-485)
2x Ethernet ports (10/100BaseT)
2x USB ports
Integrated I/O (16 binary inputs, 8 binary outputs, 8 analog inputs)
Power supply 24.... .125 VDC
(1 out of n) Check
Connection interface with RTU500 I/O expansion module
Process voltage R0001: 24...60 VDC .60 VDC
Process voltage R0002: 110... .125 VDC .125 VDC
RTU540 basic module with 2 Ethernet ports
- Metal housing
- 4 serial ports (RS-232 or RS-485)
- 2 Ethernet ports (10/100BaseT)
- USB configuration interface
- Power supply 24... 125 V DC (galvanically isolated)
- Integrated I/O (16 binary inputs, 8 binary outputs, 8 analog inputs)
- Integrated I/O (16 binary inputs, 8 binary outputs, 8 analog inputs)
- Connection interface with RTU500 I/O expansion module
- Battery-buffered real-time clock
Applications
The 540CID01 is a module in the RTU540 product family consisting of a communication unit (CMU), a multiple input/output module (IOM) and a galvanically isolated wide-range power supply (IOM).
The 540CID01 is a module in the RTU540 product family consisting of a communication unit (CMU), a multi-input/output module (IOM), and a galvanically isolated wide-range power supply (PSM) in a DIN rail metal housing.
Key tasks include
- Managing and controlling the RTU520 I/O module via the serial I/O bus
- Reading process events from the input modules
- Sending commands to the output modules.
- Communication with the control system and the local HMI system via serial and Ethernet interfaces.
- Communicates with sub-RTUs, IEDs, or multimeter devices via serial and Ethernet interfaces.
- Manages the time base of the RTU540 product line station and synchronizes the I/O modules.
- Handles the dialog between the RTU540 product line and a web browser via LAN and USB interfaces.
- Acquisition of 8 analog input signals (mA or V signals) with a fast scan cycle of 100 ms for 2 inputs - Acquisition of 16 digital input signals with a fast scan cycle of 100 ms for 2 inputs
Acquisition of 16 digital input signals, 1 high-speed counter input (max. 16 kHz)
- 8 output contacts (normally open), 1-pole or 2-pole outputs
The device is equipped with a battery-buffered real-time clock (RTC).
The device is available in two versions:
- R0001: Process voltage 24 ... 60 V DC
- R0002: Process voltage 110 ... 125 V DC 125 V DC
Input/Output Controller (IOC)
The microcontroller on the module handles all key tasks for the parameterized processing functions.
In addition, it communicates interactively with the RTU I/O bus. All configuration data and processing parameters are loaded by the communication unit via the RTU I/O bus.
The binary input unit performs the following processing functions for different types of signals:
- Digital filtering to suppress contact jumps
- Suppression of oscillating signals generated during the process
- Intermediate input state with double indication of validity check and suppression
- Consistency check of all channels assigned to digital measured values or step position information
- Summing of incremental pulses to form a combined total in a 31-bit resolution register.
- Copying of the combined total to a freeze register for data storage
The Binary Output Unit can perform the following processing functions for individual signal types:
- Control command output duration
Command monitor function:
- Output relay check on the module (m out of 8)
- Switching voltage monitoring before and during output (24 V DC coil voltage)
- Command output duration monitoring
The analog input unit performs the following processing functions on the measured values:
- Scan period and line frequency interference suppression
- Zero value monitoring and switching detection
- Smoothing
- Threshold monitoring in absolute or cumulative values
- Periodic transmission and background cycling
The module provides a data buffer for storing up to 160 event messages (including timestamps) in time.
The events are stored in a specified chronological order for transmission to the communication unit (CMU).
During initialization and operation, the module performs a series of tests. If a fault occurs, it is reported to the CMU.