PLC control of AF400 and above
Make sure the dip switch is in the correct position for proper operation See picture
below. Position A when using PLC control and position B for conventional operation (default).
High temperature readings
When concern of high temperatures on and around the contactor please check
the following (also see picture below for max permitted temperatures).
• Make sure the connections are properly torqued.
• Make sure the cable size is what is recommended in our catalogs.
• Make sure the correct coil is selected for the applications.
Measurement of the resistance of the main contacts is not recommended since only
advanced equipment can be used to get a correct reading. Due to the location of the
armature the cover can reach very high temperatures (>100C). This is still within
acceptable limits.
Transients affecting AF coils
Voltage peaks/transients are not uncom mon especially in poor quality or weak net
works. Too high voltage peaks/transients may cause damage to the AF coil. The
AF coils are designed to handle certain peaks/transients and have been tested to
meet relevant IEC standards.
Spare parts and warranty claims
Inspection intervals
The intervals between inspections are determined by the design and operating condi
tions of the contactor.
If advise is needed on a specific application please contact ABB
Spare parts
Basically these contactors are considered maintenance free. Based on reasons above
occasionally there could be a need to change certain parts. Following parts are consi
dered contactor spare parts and can be found in ABB product catalogs or on ABB web
site:
• Main contact sets
• Arc chutes (recommended to be changed at the same time as the main contacts)
• Contactor coils
• Auxiliary contact blocks
Note: Use only ABB original spare parts to ensure product reliability