Failsafe
All ControlEdge 900 Platform I/O modules support a user
specified failsafe value (analog) or state (digital) that the
module outputs or inputs will assume if communication
between the controller and the module is interrupted. Output
modules are also disabled if the controller fails to start.
Module diagnostics are not initiated if the control strategy
does not call for the inputs or outputs on the modules to execute.
Failsafe is restricted to de-energize in safety applications.
Remote Terminal Panels
Optional DIN rail mounted Remote Terminal Panels (RTPs)
are available for use with pre-wired cables to reduce installation
time and labor expense. Four types of RTPs are available:
analog inputs, relay outputs, redundant I/O and other I/O modules.
Three cable lengths are also available to match hardware to installation variations.
Analog inputs RTPs include transmitter
shunt resistors and transmitter power terminals with individual circuit fuses.
The Relay Output RTP includes a fuse and power disconnect switch for each output.
All the three types of RTP panels also switch power to allow module removal and
installation under controller power. See page 36.
Terminal Blocks
20-screw Barrier style and Euro style terminal blocks are available
for use with all ControlEdge HC900 I/O Modules.
Red terminal blocks are used for high voltage connections
for added safety while black terminal blocks are used for low voltage connections.
A 36-terminal Euro style block is available with the 16 AI, the 8 and 16 AO
as well as the 32 DC DI and 32 DC DO module types.