Features
• Full connectivity of up to 496 gensets sorted into 16 groups of 31 gensets each. One GC
3400XT per group
• Redundant or single load share communication over CAN/Ethernet between easYgen and
group controller
• Redundant or single load share communication over Ethernet among group controllers
• Redundant or single load share communication over Ethernet between GC and LS-6XT.
• Dedicated Ethernet Modbus TCP communication line to external Modbus master (PLC, SCADA
etc.)
• Active and reactive load sharing and load dependent start/stop (LDSS) management of the
whole fleet
• LDSS algorithm is emulated with a PC software and the final settings are transferred directly to
the GC
• Supports synchronization and soft loading/unloading of a tie- or mains breaker
• Phase angle compensation (Vector group adjustment) in case transformers are used in the
application
• Comprehensive monitoring of all interfaces, loss of redundancy and breaker feedback plausi
bility check
• “System Update” function for troubleshooting and fast commissioning
• Time / Date synchronization over Simple Network Time Protocol (SNTP)
• Woodward ToolKit™ software for flexible setup from a single connection to the network. The
ToolKit can be accessed either via USB, or via Ethernet, or via CAN ports..