Locations for Field Control
The Profibus Bus Interface Unit and Field Control I/O modules can be located on
equipment, in junction boxes, inside panels, behind operator stations, and in other
locations where space is limited. The area should be clean, free of airborne contaminants,
and provide adequate cooling. Field Control modules can be installed in NEMA
enclosures. The enclosure can be as little as 4 inches (10.16 cm) deep. A 35mm x 7.5mm
DIN rail is required.
The Bus Interface Unit Terminal Block and up to four I/O Terminal Blocks are grouped
together using the connection cables provided. All of the I/O Terminal Blocks in a group
must be connected either before or after the Bus Interface Unit. A Bus Interface Unit
may not be connected between I/O Terminal Blocks.
Field Control Environmental Specifications
Vibration
Noise
Temperature
Humidity
Modules perform well where vibration is a factor. Modules are installed
on a panel-mounted DIN rail using the clamp supplied, and with the
panel-mounting feet secured. For information about vibration
standards, please see the Conformance to Standards document (GFK-1179).
Modules are resistant to noise levels found in most industrial applications
when installed according to accepted practices, including proper separation
of wiring by voltage and power level. Modules must be installed on a
conductive (unpainted) DIN rail. The DIN rail is an integral part of the
grounding system.
Modules are tested to the specifications listed in the Conformance to
Standards document (GFK-1179).
Modules operate reliably in ambient air temperatures from 0C (32F)
up to 55C (131F).
Storage temperatures are ±40C (±40F) to +85C (185F).
5% to 95%, non-condensing.
For detailed installation information, please see:
Chapter 2 of this manual. It describes installation and wiring for the Bus Interface
Unit module and terminal block.
Chapter 2 of the Field Control I/O Modules User's Manual. It summarizes installation
instructions for modules and terminal blocks. Detailed installation instructions are
also packed with individual Field Control modules.
The individual module datasheets included in the Field Control I/O Modules User's
Manual, which provide specific module wiring information.
Conformance to Standards (GFK-1179). This manual describes the installation
requirements for programmable control products used in industrial environments,
specifically, in situations where compliance to standards or directives from the
Federal Communications Commission, the Canadian Department of
Communications, or the European Union is necessary. The information in this
manual is applicable for GE Fanuc Series 90-70 and Series 90-30 programmable
controller products, Genius I/O products, and Field Control Distributed I/O and Control products.
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved