FP-4000 Product Description
• Microprocessor-based protection with monitoring and control for
medium voltage main and feeder breakers.
• Current, voltage and frequency protection for electric power
distribution systems.
• Complete metering of voltage, currents, power, energy,
minimum/maximum and demand functions.
• Programmable logic control functions for main-tie-main
transfer schemes.
• Trip logs, event logs and waveform capture for better fault analysis
and system restoration.
• Data Logger to provide energy usage profiles for better planning,
utilization and energy usage.
• Fixed case design.
• Meets ANSI and UL standards.

Application Description
Eaton’s Cutler-Hammer FP-4000 Feeder Protection Relay provides
complete 3-phase and ground overcurrent and voltage protection
plus metering. It may be used as primary protection on feeders, mains
and tie circuit breaker applications, and as backup protection for trans
formers, high voltage lines and differential protection. The relay is most
commonly used on medium voltage switchgear applications.
The FP-4000 takes full advantage of its microprocessor technology,
providing the user new freedoms and a wealth of data-gathering
features. The relay performs self-checking of all major hardware and
firmware protection elements to ensure their operation in the event of
a system or component electrical failure or fault. Protection functions
are well suited for main and distribution feeder circuit applications.
Programmable logic control functions make the FP-4000 relay ideally
suited for main-tie-main and main 1/main 2 transfer schemes.
The zone interlocking feature can be utilized for bus protection instead
of an expensive and complicated bus differential (87B) scheme.
The FP-4000 works directly with the Cutler-Hammer Digitrip 3000
and Digitrip MV relays. New breaker failure logic provides faster
remote backup clearing times for stuck breaker operation.
The FP-4000 provides trip and close circuit monitoring and alarming
features. It continually monitors the complete trip and close circuits
for continuity and readiness to trip. Open and close pushbuttons are
conveniently located on the front of the relay for local breaker operation.
Loss-of-vacuum monitoring is activated when the breaker is open.
Residual current is monitored and alarmed if detected.
When an electrical fault or disturbance occurs, the FP-4000 begins
to store the following in non-volatile memory:
• Voltage and current sampled data.
• Calculated values.
• Status of internal protection functions, logic, contact inputs and
outputs.
Retrieval and viewing of the data is easy, aiding in the quick analysis
and restoration of your electric power system.
When the FP-4000 isn’t responding to disturbances in the power
system, it’s providing valuable metering information at the relay and
remotely. It provides energy usage and demand reading, and can
alarm when usage reaches a set value. Power factor measurements
can be used for cap bank switching to control kvar demand.
Onboard data trending can provide load profiles for up to 40 days.
The protection functions are listed below and shown in Figure 1.
The FP-4000 provides phase overcurrent:
• Two-stage instantaneous with timers (50P-1 and 50P-2).
• Inverse time overcurrent (51P-1).
• 10 standard curves.
• Instantaneous or time delay reset.