Communications
The FB2200 provides up to five user-selectable
communications ports: three serial ports, one Ethernet
port, and one optional port that supports FBxWifi
(802.11 b/g) communications using DNP3 protocol.
▪ COM1 – 4-wire serial communications. Software
selectable for EIA-232 (RS-232), EIA-422 (RS-422), or
EIA-485 (RS-485) operation.
▪ COM2 – 2-wire serial communications. Software
selectable for EIA-232 (RS-232) or EIA-485 (RS-485)
operation.
▪ COM3 – 2-wire serial communications. Software
selectable for EIA-232 (RS-232) or EIA-485 (RS-485)
operation.
▪ COM4 –FBxWifi (802.11 b/g) communications
(optional).
▪ COM5 – Ethernet. 10/100BASE-T twisted pair.
Supports up to seven sessions.
Communications Protocols
The FB2200 supports multiple communications
protocols, including DNP3. Modbus master and slave
(ASCII and RTU), BSAP, and ROC on the three serial
ports. In addition, the Ethernet port supports RTU
Modbus over TCP/IP protocol (master and slave),
DNP3/IP, ROC and BSAP.
FBxNet™
FBxNet is a secure, easily configurable, peer-to-peer
communication network for exchanging data between
Emerson FB3000 RTUs and FB1200 and FB2200 flow
computers over an Ethernet connection. FBxNet
supports subscriber and publisher devices, where
publishers provide data to their subscribers. The
FB3000 RTUs and FB1200 and FB2200 flow computers
can be publishers; only an FB3000 can be a subscriber.
For more information, refer to product data sheet
FBxNet (part D301905X012).
Mounting Options
The FB2200 supports direct mounting to a manifold on
the pipeline, simple wall mounting, or mounting on a
two-inch pipe with the stainless steel pipe mounting kit.