OVERVIEW
The F880 redundant fieldbus power supply is designed to provide redundant power
for eight (8) Foundation fieldbusTM H1 segments. Connections are provided on the
F880-Cx Carrier for two redundant pairs of Yokogawa ALF111 fieldbus cards using
Yokogawa AKB336 cables. Power for the eight fieldbus segments is provided by two
F801 or F802 Power Modules mounted to the carrier and operating in a redundant
configuration. Failure alarms, galvanic isolation, power conditioning and segment
termination are incorporated into each Power Module. A single Power Module may
be used where redundancy is not required.

DESCRIPTION
For maximum reliability, the module carrier contains no components and only provides
interconnections between the power modules and the external connections. The
carrier circuit board is supported in a rigid metal frame that protects it from mechanical
damage. Secure DIN-rail mounting is provided by integrated fixings. The F801 or
F802 module provides galvanic isolation between the 24V DC input power and the
fieldbus segments, as required by the IEC61158-2 fieldbus standard and the Fieldbus
FoundationTM FF-831 validation test for fieldbus power supplies. There is also galvanic
isolation between the fieldbus segments, thereby preventing cross-talk between
segments in the event of ground faults in the field wiring. Each segment has its own
current limitation and passive fieldbus power conditioner. Termination of the fieldbus
segment is automatically maintained when single or redundant F801 or F802 modules
are fitted. The F880-Cx carrier is equipped with connectors that will accept an F809F
diagnostic module. The module continuously monitors the performance of each of the
eight fieldbus segments, providing information on the network health.
Each Power Module has indicator LEDs to show both its status and that of the eight
segments under power. In normal operation, each green ‘Segment’ LED is lit, showing
that the segment is powered. If a segment is shorted, or its voltage is below the rated
output, its LED is extinguished, and the red ‘Alarm’ LED is lit. Redundant 24V DC (nom.)
input power is connected to the F880-Cx carrier using two-part pluggable connectors.
Field wiring connections are available with either pluggable screw terminals (F880-*S)
or pluggable spring clamp terminals (F880-*C).
Three variants of carriers are available in the F880 family to be used in two different
types of installations. For large installations where multiple F880 systems will be
installed in a cabinet, there are Left (F880-CL) and Right hand (F880-CR) versions
that make cabinet wiring symmetrical – see Figure 2b. In smaller installations where
carriers are not installed side-by-side, the F880-CA carrier provides terminal numbering
and consistent connector polarity.