Introduction
This document is designed to assist and guide a trained technician or engineer to diagnose and
troubleshoot the Smart Equipment Controller alarms. When troubleshooting always use Johnson
Controls and industry safety standards.

Preliminary checks
No power
The Smart Equipment™ Control (SEC) board requires 24 VAC to operate. If no power is provided then
no alarms are active, the LCD screen is blank, and the unit does not function at all.
1.on the upper left hand of the board using the voltmeter.--
If no voltage is present, check the wiring diagram and trace where the 24 VAC power is
lost.
If voltage is present and no power is indicated on the SEC board through the LCD
display or power LED indicator, replace the board.
2.Check for optional components such as the phase monitor in the circuit. If there is a red light
visible on the phase monitor, this indicates that the board is not receiving power. Swap the
incoming voltage going to the unit, not the voltage within the unit.
Heating alarms
HS1 lockout due to limit switch
The HS1 Lockout occurs due to a loss of 24 VAC to the SEC board LIMIT terminal. The LIMIT circuit
will have two or more limit switches wired in series. One switch is an automatic limit switch and
the other is a manual limit switch. If the SEC board recognizes three limit switch trips in one hour a
hard lockout of unit operation occurs and no operation occurs other than blower operation.
If a HS1 Lockout occurs complete the following steps:
1. Use a volt meter to check that 24 VAC power is present at the LIMIT terminal located on at the
upper left corner of the SEC board.
a. If no voltage is present, check the wiring diagram and trace where the 24 VAC power
is lost.
b. If voltage is present, continue to Step 2.
2. Determine if a limit switch is open and check the possible cause of the limit trip.
3. Check the circuit wiring for damage or a loose connection.
4. Check if the limit switch is faulty. If the switch is tripping without reaching tripping
temperature, this can indicate a faulty LIMIT switch.
5. Check that all the filters are clean.
6. Check for correct air flow according to the unit installation manual. Return static should not
be higher than 0.2 in. w.c. Factory equipment should be air balanced to operate in a cfm
range from 350 cfm to 450 cfm per ton.
Note:
a. If the unit AHU or RTU is a VAV application during the heating operation, the fan
should run at an adequate speed to allow correct air flow that will prevent the
unit from tripping on HS1 lockout. This means in most cases the VAV boxes must
be open when a call for heat is commanded.
b. On occasions where the system has two transformers, proper low voltage
phasing must be verified or HS1 could occur.
wechat/whatsapp:
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved