DualControl (Power Bridge Warm Backup)
The EX2100e Regulator system is available in a warm backup (WBU) configuration,
which includes dual exciter control I/O and protection. The control includes M1 (Master
One) and M2 (Master Two), with two IGBT bridges that can accept separate or shared ac
input power. The control configuration can also share a common dc output circuit to the
exciter field through the transfer module. M1 and M2 are independent controls, each with
automatic and manual regulator functions. Either M1 or M2 can control bridge firing, as
determined by the operator. In the WBU configuration, M1 controls bridge #1. and M2
controls bridge #2.
To process application software, two independent Universal Controller Stand-alone Board
Version B (UCSB) controllers, with separate PCMs and an output selector module (SCM
or TCM), provide the dc output current for the exciter field (or SCTcontrol winding).
The active power bridge receives the gating commands from the active control (M1 or
M2), and supports the full-field voltage and current needs of the exciter field while the
backup power bridge’s gating circuit is inhibited. The operator has full control to select
which of the dual power bridges is active or inactive. Bi-directional, bumpless transfer
between active and inactive bridges is standard. The active master can also self-diagnose
a failure or missed operation and activate the backup control and power bridge without
operator intervention.