The ELX2792 output terminal has two relays, each with a
changeover contact, which can be used universally to
switch intrinsically safe loads up to zone 0/20.

These could be, for example, solenoid valves, contactors
or optical/acoustic signal devices. The ELX2792 features
potential-free contacts. The signal state of each individual
channel is displayed by an LED. EtherCAT Terminals from
the ELX series must always be operated in conjunction
with the ELX9560 power feed terminal, which generates
an electrically isolated output voltage (24 V EX) from the
input voltage (24 V DC) to supply the downstream ELX
terminals. If a renewed feed-in should be necessary,
the combination of an ELX9410 and an ELX9560 can be
used so that further ELX terminals can be connected inline.
The ELX terminal segment must be terminated with one
ELX9012. two ELX9410 or one EK1110.
The use of two ELX9410 allows the use of EL terminals
behind ELX terminals. With the EK1110. the terminal
segment can be continued via an EtherCAT cable,
for example to implement cable redundancy.