The EL3453-0120 EtherCAT power measurement terminal has voltage
inputs for up to 130 V AC for connecting voltage transducers, enabling
the monitoring of medium-voltage systems, for example.
The four current inputs are electrically isolated so that the terminal can
be used in all common grounded current transformer configurations
such as 2- or 3-transformer configurations with star or delta connection
incl. neutral conductor current measurement. The EL3453-0120 can be
used for simple grid analysis up to the 63rd harmonics analysis.

Alternatively, all readings can be combined in a power quality factor for
simplified diagnostics. Like all measured terminal data, the harmonic
content can be read via the process data. The EL3453-0120 offers the
“ExtendedRange” feature enabling the use of the full technical measuring
range, which equals 130% of the specified nominal measuring range.
In addition, the EL3453-0120 comes with the option of transmitting the
times of the last voltage and current zero crossing to the controller via
XFC technology. This can be used, for example, to carry out switching
operations to suit the application.
The individual Beckhoff factory calibration certificate can be downloaded
via Beckhoff Service.